Details on ELMBs

   35 ATMEGA128L ELMBs are connected to 2 CANbus lines with total length of approx 330 m. To avoid cross-talk between different detectors and their electronics, it was decided to have independent ELMBs for each detectors or sub-system, whenever possible. The distribution of the ELMBs over the experimental hall is optimized in order to have the shortest wiring connections to sensors or monitoring points.

   The monitoring is done using CANOpen OPC Server (CanOpc.exe), running on PCCOMPASS08 (Windows XP), installed in DCS room HNB423. The configuration file for the OPC Server is located in the "OPC" directory. A PVSS API manager "PVSS00opc -num 7", as a client, connects to the OPCCanOpen Server. 2 ports of a Kvaser PCI-CAN Q (4 ports) interface card are used (the card is in 4 indepent ports configuration). The CANbus network consists of 2 CANbus branches, of 120 m and 210 m. Due to their long length (>50 m), cable with 6 conducting wires with cross-section 0.5 mm2 for each is used for CANbus1 and CANbus2 (multiconductor screened cable layer twisted, CERN catalogue - 04.21.51.106.0).

  
A special transition board is used for the ELMB connection to the network cable (see the scheme here). The wires of thick cable are ended by pins and screws on board contacts, which has printed wiring between to Dsub 9 pin connector. The ELMB CANbus connector connects to the transition board via a short(0,5 m) flat cable.

   Each ELMB has its own local power supply and there is only one central power supply for the CANbus. The system has full optocoupling between nodes connected to CANbus line. The power supply for the CANbus provides 12V and a current of 1.5-2 Amps, being located in the DCS room, close to the PCCOMPASS08. This powers the CANbus receivers/transmitters, which are optically insulated from the ELMB internal circuit. The ELMBs have their own local power supplies. As a rule, each ELMB has a power supply for its analog part and another for the digital part. In some cases one common power supply is used for both parts. The nominal voltage of the power supplies is 12V. There are 2 types of power supplies used as local: Switching power supply OMRON model S82K with 12V output, Imax=1.5A (mounted in a rail and with protection cover); and Regulated Adapter type EP2, FRIWO with output 12V, Imax=0.5A.

   Plugged to the ELMB's motherboard, 2 types of adapters are used, depending of the input signals to the ELMB: High performance Pt100 adapters, with Rc = 3.9 KOhm, Rs = 100 Ohm (to be used with Pt4w temperature sensors); and Differential attenuators with 1:100 divider (100 KOhm/1 KOhm).

   Different kinds of sensors are used, depending on the parameters to be monitored. For temperature measurements we use Pt100 sensors. The humidity measurements are done using type HIH 3605A humidity sensors. For pressure measurements, type 144S PCB Series is used. The magnetic field is measured with UGN35 Hall probe.

   In PVSS, there are several monitoring parameters with associated alarm signals defined (so that an alarm will be displayed if the read value goes out of a given min/max threshold). The alarm causes changing the background colour of the alarm text window, from green to orange or red. Also, the alarm signal will be propagated to the top of the monitoring system hierarchy and cause changing the colour of the associated detector button on the main COMPASS control panel.

   The monitoring parameters that can produce alarm signals are:

  • TARGET, RICH, MM, DC4, STRAWs, W45, MW1 and ECAL1 Temperature Sensors;

  • LV from MW1, MW2, MWPCs, ECAL1 and ECAL2;

  • MW2_gas_alarm. This parameter represents the status of gas system for MW2 detector;

  • SM1_M_F. Measurement of the stability of SM1 magnetic field - Magnets panel;

  • B6_M_F. Measurement of the stability of B6 magnetic field - Magnets panel;

  • SM2 Measurement from the NMR - Magnets panel;

  • Hall pressure - Environment Panel;

  • DAQ and Tigger room temperatures - Environment panel;

    Supply water temperature of raw water circuit (for cooling of Straws, MM and DC) - Environment panel;

    Water temperature of tank for water circuit that homegenizes temperature of DC4 frame - DC>DC4>Temperatures panel;

  • T_W_DEP; T_W_RET. These 2 parameters represent the temperatures of incoming and outgoing water in the RICH electronics cooling system - Environment panel.
     

  • Ecal1_Laser_isOn - ECAL1 panel.
     



ELMBs configuration

Jump to ELMB #:
1    2    3    4    5    6    7    8    9    10    11    12    13    14    15    16    17    18    19    20    22    23    24    25    29    30    31    32    33    34    35   
  • ELMB #1
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: Gallerie;
    Measurements: LV from RICH Wall.
    Status: Installed but not connected to detector.
  • ELMB #2

  • CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: MW1 FE LV power supply rack, SM2 region, Jura side.
    Status: installed
    Comments: Cable entering ELMB channels 0-15 labelled "ADC input 1"; to channels 16-31 labelled "ADC input 3"; to channels 32-47 labelled "ADC input 2". In PVSS the factors 0.6, 1.4 and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
    ADC channels Dp name Comments Status
    0 mW1_C31_5Vp Crate #3, +5V, channel 1 ON
    1 mW1_C31_5Vn Crate #3, -5V, channel 1 ON
    2 mW1_C32_5Vp Crate #3, +5V, channel 2 ON
    3 mW1_C32_5Vn Crate #3, -5V, channel 2 ON
    4 mW1_C41_5Vp Crate #4, +5V, channel 1 ON
    5 mW1_C41_5Vn Crate #4, -5V, channel 1 ON
    6 mW1_C42_5Vp Crate #4, +5V, channel 2 ON
    7 mW1_C42_5Vn Crate #4, -5V, channel 2 ON
    8 mW1_C51_5Vp Crate #5, +5V, channel 1 ON
    9 mW1_C51_5Vn Crate #5, -5V, channel 1 ON
    11 mW1_C52_5Vp Crate #5, +5V, channel 2 ON
    12 mW1_C52_5Vn Crate #5, -5V, channel 2 ON
    16 mW1_V3_5Vp Crate VME #3, +5V voltage ON
    17 mW1_V3_5Ip Crate VME #3, +5V current ON
    18 mW1_V3_12Vp Crate VME #3, +12V voltage ON
    19 mW1_V3_12Ip Crate VME #3, +12V current ON
    20 mW1_V3_12Vn Crate VME #3, -12V voltage ON
    21 mW1_V3_12In Crate VME #3, -12V current ON
    22 mW1_V3_OVT Crate VME #3 PS Over-Temperature ON
    23 mW1_V3_OLD Crate VME #3 cards Over- temperature ON
    24 mW1_V1_5Vp Crate VME #1, +5V voltage ON
    33 mW1_V1_5Ip Crate VME #1, +5V current ON
    34 mW1_V1_12Vp Crate VME #1, +12V voltage ON
    35 mW1_V1_12Ip Crate VME #1, +12V current ON
    36 mW1_V1_12Vn Crate VME #1, -12V voltage ON
    37 mW1_V1_12In Crate VME #1, -12V current ON
    38 mW1_V1_OVT Crate VME #1 PS Over-Temperature ON
    39 mW1_V1_OLD Crate VME #1 cards Over- temperature ON
    40 mW1_V2_5Vp Crate VME #2, +5V voltage ON
    41 mW1_V2_5Ip Crate VME #2, +5V current ON
    42 mW1_V2_12Vp Crate VME #2, +12V voltage ON
    43 mW1_V2_12Ip Crate VME #2, +12V current ON
    44 mW1_V2_12Vn Crate VME #2, -12V voltage ON
    45 mW1_V2_12In Crate VME #2, -12V current ON
    46 mW1_V2_OVT Crate VME #2 PS Over-Temperature ON
    47 mW1_V2_OLD Crate VME #2 cards Over- temperature ON
    58 - 59 T_Mw1_Lv_Crates_Jura Pt4w temperature sensor ON
    60 - 61 T_Mw1_Jura_Floor Pt4w temperature sensor, T2' ON
    62 - 63 pt4w_elmb2_T63 Pt4w temperature sensor, T2 ON


  • ELMB #3
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: BMS electronics room.
    Status: installed.
    ADC channels Dp name Comments Status
    32 mW2_gas_alarm Gas alarm from MW2 gas system ON
    36 ecal2_hv_signal HV system alarm for ECAL2 ON
    60 - 61 T_W_RET Pt4w temp sensor, incoming water for RICH electronics cooling ON
    62 - 63 T_W_DEP Pt4w temp sensor, outgoing water from RICH electronics cooling ON

  • ELMB #4
    CANbus line #2
    ADC mode: unipolar; ADC range: 1 V.
    Place: MW1 FE LV power supply rack, SM2 region, Saleve side.
    Status: installed.
    Comments: In PVSS the factors 0.6, 1.4 and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
    ADC channels Dp name Comments Status
    1 mW1_C11_5p Crate #1, +5V, channel 1 ON
    2 mW1_C11_5n Crate #1, -5V, channel 1 ON
    3 mW1_C12_5p Crate #1, +5V, channel 2 ON
    4 mW1_C12_5n Crate #1, -5V, channel 2 ON
    5 mW1_C21_5p Crate #2, +5V, channel 1 ON
    6 mW1_C21_5n Crate #2, -5V, channel 1 ON
    7 mW1_C22_5p Crate #2, +5V, channel 2 ON
    8 mW1_C22_5n Crate #2, -5V, channel 2 ON
    16 mW1_V4_5Vp Crate VME #4, +5V voltage ON
    17 mW1_V4_5Ip Crate VME #4, +5V current ON
    18 mW1_V4_12Vp Crate VME #4, +12V voltage ON
    19 mW1_V4_12Ip Crate VME #4, +12V current ON
    20 mW1_V4_12Vn Crate VME #4, -12V voltage ON
    21 mW1_V4_12In Crate VME #4, -12V current ON
    22 mW1_V4_OVT Crate VME #4 PS Over-Temperature ON
    23 mW1_V4_OLD Crate VME #4 cards Over-Temperature ON
    24 mW1_V5_5Vp Crate VME #5, +5V voltage ON
    25 mW1_V5_5Ip Crate VME #5, +5V current ON
    26 mW1_V5_12Vp Crate VME #5, +12V voltage ON
    27 mW1_V5_12Ip Crate VME #5, +12V current ON
    28 mW1_V5_12Vn Crate VME #5, -12V voltage ON
    29 mW1_V5_12In Crate VME #5, -12V current ON
    30 mW1_V5_OVT Crate VME #5 PS Over-Temperature ON
    31 mW1_V5_OLD Crate VME #5 cards Over-Temperature ON
    62 - 63 T_Mw1_Lv_Crates_Saleve Pt4w temperature sensor ON

  • ELMB #5
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: SciFiG FE LV power supply rack, SM2 region, Saleve side.
    Status: installed
    ADC channels Dp name Comments Status
    60 - 61 Mag_Sm1_T_Surface Pt4w temperature sensor ON
    62 - 63 pt4w_elmb5_T63 Temperature inside hall 888 (1.5 m away from rack), T5 ON

  • ELMB #6
    CANbus line #2
    ADC mode: unipolar; ADC range: 100mV.
    Place: STRAW frame, temperature and humidity sensors, Jura side.
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 STO3V2_TDS Pt4w temperature sensor ON
    2 - 3 STO3V2_TDM Pt4w temperature sensor ON
    4 - 5 STO3V2_TDJ Pt4w temperature sensor ON
    6 - 7 STO3V2_TMS Pt4w temperature sensor ON
    8 - 9 STO3V2_TMJ Pt4w temperature sensor ON
    10 - 11 STO3V2_TUS Pt4w temperature sensor ON
    12 - 13 STO3V2_TUM Pt4w temperature sensor ON
    14 - 15 STO3V2_TUJ Pt4w temperature sensor ON
    16 - 17 STO3Y2_TDS Pt4w temperature sensor ON
    18 - 19 STO3Y2_TDM Pt4w temperature sensor ON
    20 - 21 STO3Y2_TDJ Pt4w temperature sensor ON
    22 - 23 STO3Y2_TMS Pt4w temperature sensor ON
    24 - 25 STO3Y2_TMJ Pt4w temperature sensor ON
    26 - 27 STO3Y2_TUS Pt4w temperature sensor ON
    28 - 29 STO3Y2_TUM Pt4w temperature sensor ON
    30 - 31 STO3Y2_TUJ Pt4w temperature sensor ON
    32 - 33 STO3X2_TDS Pt4w temperature sensor ON
    34 - 35 STO3X2_TDM Pt4w temperature sensor ON
    36 - 37 STO3X2_TDJ Pt4w temperature sensor ON
    38 - 39 STO3X2_TMS Pt4w temperature sensor ON
    40 - 41 STO3X2_TMJ Pt4w temperature sensor ON
    42 - 43 STO3X2_TUS Pt4w temperature sensor ON
    44 - 45 STO3X2_TUM Pt4w temperature sensor ON
    46 - 47 STO3X2_TUJ Pt4w temperature sensor ON
    48 STO3V2_H Humidity sensor ON
    49 STO3X2_H Humidity sensor ON
    50 STO3Y2_H Humidity sensor ON
    51 STO3X1_H Humidity sensor ON
    52 STO3U1_H Humidity sensor ON
    53 STO3Y1_H Humidity sensor ON

  • ELMB #7
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: RICH rack; temperature sensors inside RICH vessel, Saleve side, and inside ECal1 cassettes, downstream side, top center and top Jura.
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 pt4w-RICH-1 Pt4w temperature sensor inside vessel OFF
    2 - 3 pt4w-RICH-2 Pt4w temperature sensor inside vessel OFF
    4 - 5 pt4w-RICH-3 Pt4w temperature sensor inside vessel ON
    6 - 7 pt4w-RICH-4 Pt4w temperature sensor inside vessel ON
    8 - 9 pt4w-RICH-5 Pt4w temperature sensor inside vessel ON
    10 - 11 pt4w-RICH-6 Pt4w temperature sensor inside vessel ON
    12 - 13 pt4w-RICH-7 Pt4w temperature sensor inside vessel ON
    14 - 15 pt4w-RICH-8 Pt4w temperature sensor inside vessel ON
    16 - 17 pt4w-RICH-9 Pt4w temperature sensor inside vessel ON
    18 - 19 pt4w-RICH-10 Pt4w temperature sensor inside vessel ON
    20 - 21 pt4w-RICH-11 Pt4w temperature sensor inside vessel ON
    22 - 23 pt4w-RICH-12 Pt4w temperature sensor inside vessel ON
    24 - 25 pt4w-RICH-13 Pt4w temperature sensor inside vessel ON
    26 - 27 pt4w-RICH-14 Pt4w temperature sensor inside vessel ON
    28 - 29 pt4w-RICH-15 Pt4w temperature sensor inside vessel ON
    30 - 31 pt4w-RICH-16 Pt4w temperature sensor inside vessel ON
    32 - 33 pt4w-RICH-17 Pt4w temperature sensor inside vessel ON
    34 - 35 pt4w-RICH-18 Pt4w temperature sensor inside vessel ON
    48 - 49 PT_4W_48_49 Pt4w temperature sensor in ECal1 downstream side, Gams Saleve middle ON
    50 - 51 PT_4W_50_51 Pt4w temperature sensor in ECal1 downstream side, Mainz Saleve top ON
    52 - 53 PT_4W_52_53 Pt4w temperature sensor in ECal1 downstream side, Olga Jura top ON
    54 - 55 PT_4W_54_55 Pt4w temperature sensor in ECal1 downstream side, Olga Jura middle ON
    62 - 63 pt4w-elmb7-T63 Pt4w sensor: temperature inside hall 888, T7 ON

  • ELMB #8
    CANbus line #2
    ADC mode: bipolar; ADC range: 100 mV.
    Place: SciFi rack, Saleve side.
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 PT_1_HSO Pt4w temp sensor, Pol Target horizontal screen outlet ON
    2 - 3 PT_2_DTF Pt4w temp sensor, Pol Target dilution cryostat top flange ON
    4 - 5 PT_3_SLT Pt4w temp sensor, Pol Target still line top ON
    6 - 7 PT_4_MHG Pt4w temp sensor, Pol Target magnet gas outlet OFF
    8 - 9 PT_5_SCW Pt4w temp sensor, Pol Target magnet downstream neck ON
    10 - 11 PT_6_SFC Pt4w temp sensor, Pol Target separator flow control ON
    12 - 13 PT_7_NMR Pt4w temp sensor, Pol Target NMR rack ON
    14 - 15 PT_8_SCL Pt4w temp sensor, Pol Target magnet upstream neck ON
    16 SM1_M_F Hall probe for SM1 Magnetic field ON
    28 - 29 PT_4W_28_29 Pt4w temp sensor, LH2 target gas control panel OFF
    30 - 31 PT_4W_30_31 Pt4w temp sensor, LH2 target hidrogen tank OFF
    32 - 33 SI01_T_u1 Pt4w temp sensor OFF
    34 - 35 SI01_T_u2 Pt4w temp sensor ON
    36 - 37 SI02_T_u1 Pt4w temp sensor ON
    38 - 39 SI02_T_u2 Pt4w temp sensor ON
    40 - 41 SI02_T_y1 Pt4w temp sensor ON
    42 - 43 SI02_T_y2 Pt4w temp sensor ON
    44 - 45 SI01_T_x1 Pt4w temp sensor ON
    46 - 47 SI01_T_x2 Pt4w temp sensor ON
    48 - 49 SI03_T_u1 Pt4w temp sensor ON
    50 - 51 SI03_T_u2 Pt4w temp sensor ON
    52 - 53 SI02_T_v1 Pt4w temp sensor OFF
    54 - 55 SI02_T_v2 Pt4w temp sensor OFF
    56 - 57 SI03_T_y1 Pt4w temp sensor ON
    58 - 59 SI03_T_y2 Pt4w temp sensor ON
    60 - 61 SI02_T_x1 Pt4w temp sensor ON
    62 - 63 pt4w_elmb8_T63 Pt4w temperature sensor inside hall 888, T8 ON

  • ELMB #9
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: BMS HV room HNB 202.
    Status: installed.
    ADC channels Dp name Comments Status
    0 B6_M_F sensor on Bending Magnet B6 ON
    16 - 17 PT_4W_16_17 Pt4w sensor, CEDAR1 tent temperature ON
    18 - 19 PT_4W_19_19 Pt4w sensor, CEDAR1 tent temperature ON
    20 - 21 PT_4W_20_21 Pt4w sensor, CEDAR1 tent temperature ON
    22 - 23 PT_4W_22_23 Pt4w sensor, CEDAR1 tent temperature ON
    24 - 25 PT_4W_24_25 Pt4w sensor, CEDAR1 tent temperature ON
    26 - 27 PT_4W_26_27 Pt4w sensor, CEDAR1 tent temperature ON
    28 - 29 PT_4W_28_29 Pt4w sensor, CEDAR1 tent temperature ON
    30 - 31 PT_4W_30_31 Pt4w sensor, CEDAR1 tent temperature ON
    32 - 33 PT_4W_32_33 Pt4w sensor, CEDAR2 tent temperature ON
    34 - 35 PT_4W_34_35 Pt4w sensor, CEDAR2 tent temperature ON
    36 - 37 PT_4W_36_37 Pt4w sensor, CEDAR2 tent temperature ON
    38 - 39 PT_4W_38_39 Pt4w sensor, CEDAR2 tent temperature ON
    40 - 41 PT_4W_40_41 Pt4w sensor, CEDAR2 tent temperature ON
    42 - 43 PT_4W_42_43 Pt4w sensor, CEDAR2 tent temperature ON
    44 - 45 PT_4W_44_45 Pt4w sensor, CEDAR2 tent temperature ON
    46 - 47 PT_4W_66_47 Pt4w sensor, CEDAR2 tent temperature ON
    60 - 61 AirTemp Pt4w sensor, Air temperature outside building 888 ON
    62 - 63 T_OUT_SIDE Pt4w sensor, temperature inside BMS room ON

  • ELMB #10
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, mMegas/Drifts electronics rack
    Status: installed
    ADC channels Dp name Comments Status
    0 - 1 MM03_UV_1 Pt4w temperature sensor for MM ON
    2 - 3 MM03_UV_2 Pt4w temperature sensor for MM ON
    4 - 5 MM03_UV_3 Pt4w temperature sensor for MM ON
    6 - 7 MM03_UV_4 Pt4w temperature sensor for MM ON
    8 - 9 MM03_XY_1 Pt4w temperature sensor for MM ON
    10 - 11 MM03_XY_2 Pt4w temperature sensor for MM ON
    12 - 13 MM03_XY_3 Pt4w temperature sensor for MM ON
    14 - 15 MM03_XY_4 Pt4w temperature sensor for MM ON
    16 - 17 MM01_UV_1 Pt4w temperature sensor for MM ON
    18 - 19 MM01_UV_2 Pt4w temperature sensor for MM ON
    20 - 21 MM01_UV_3 Pt4w temperature sensor for MM OFF
    22 - 23 MM01_UV_4 Pt4w temperature sensor for MM ON
    24 - 25 MM01_XY_1 Pt4w temperature sensor for MM OFF
    26 - 27 MM01_XY_2 Pt4w temperature sensor for MM OFF
    28 - 29 MM01_XY_3 Pt4w temperature sensor for MM OFF
    30 - 31 MM01_XY_4 Pt4w temperature sensor for MM OFF
    32 - 33 MM02_XY_1 Pt4w temperature sensor for MM OFF
    34 - 35 MM02_XY_2 Pt4w temperature sensor for MM OFF
    36 - 37 MM02_UV_3 Pt4w temperature sensor for MM ON
    38 - 39 MM02_UV_4 Pt4w temperature sensor for MM OFF
    40 - 41 MM02_XY_1 Pt4w temperature sensor for MM ON
    42 - 43 MM02_XY_2 Pt4w temperature sensor for MM ON
    44 - 45 MM02_XY_3 Pt4w temperature sensor for MM ON
    46 - 47 MM02_XY_4 Pt4w temperature sensor for MM ON
    58 Hum1_HALL Humidity sensor ON
    69 Patm_hall Atmospheric pressure sensor ON
    60 - 61 Mag_Sm1_T_Surface Pt4w temperature sensor ON
    62 - 63 pt4w-elmb10-T63 Temperature sensor, point T10 ON

  • ELMB #11
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 rack

    Comments: Stations 7 and 11 are not connected since the power supplies have moved from MWPC to W45 rack.
    Status: installed

    ADC channels Dp name Comments Status
    0 mwpc_8X_6v_vmon Low voltage for MWPC station 8 ON
    1 mwpc_8X_6v_imon Low voltage for MWPC station 8 ON
    2 mwpc_8X_9v_vmon Low voltage for MWPC station 8 ON
    3 mwpc_8X_9v_imon Low voltage for MWPC station 8 ON
    4 mwpc_7X_6v_vmon Low voltage for MWPC station 7 OFF
    5 mwpc_7X_6v_imon Low voltage for MWPC station 7 OFF
    6 mwpc_7X_9v_vmon Low voltage for MWPC station 7 OFF
    7 mwpc_7X_9v_imon Low voltage for MWPC station 7 OFF
    8 mwpc_7V_6v_vmon Low voltage for MWPC station 7 OFF
    9 mwpc_7V_6v_imon Low voltage for MWPC station 7 OFF
    10 mwpc_7V_9v_vmon Low voltage for MWPC station 7 OFF
    11 mwpc_7V_9v_imon Low voltage for MWPC station 7 OFF
    12 mwpc_7U_6v_vmon Low voltage for MWPC station 7 OFF
    13 mwpc_7U_6v_imon Low voltage for MWPC station 7 OFF
    14 mwpc_7U_9v_vmon Low voltage for MWPC station 7 OFF
    15 mwpc_7U_9v_imon Low voltage for MWPC station 7 OFF
    16 mwpc_11U_6v_vmon Low voltage for MWPC station 11 OFF
    17 mwpc_11U_6v_imon Low voltage for MWPC station 11 OFF
    18 mwpc_11U_9v_vmon Low voltage for MWPC station 11 OFF
    19 mwpc_11U_9v_imon Low voltage for MWPC station 11 OFF
    20 mwpc_11V_6v_vmon Low voltage for MWPC station 11 OFF
    21 mwpc_11V_6v_imon Low voltage for MWPC station 11 OFF
    22 mwpc_11V_9v_vmon Low voltage for MWPC station 11 OFF
    23 mwpc_11V_9v_imon Low voltage for MWPC station 11 OFF
    24 mwpc_11X_6v_vmon Low voltage for MWPC station 11 OFF
    25 mwpc_11X_6v_imon Low voltage for MWPC station 11 OFF
    26 mwpc_11X_9v_vmon Low voltage for MWPC station 11 OFF
    27 mwpc_11X_9v_imon Low voltage for MWPC station 11 OFF
    62 - 63 pt4w-elmb11-T63 Temperature sensor, T11 ON


  • ELMB #12
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack
    Status: installed
    Comments: ELMB #11 and ELMB #12 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    0 mwpc_10V_6v_vmon Low voltage for MWPC station 10 ON
    1 mwpc_10V_6v_imon Low voltage for MWPC station 10 ON
    2 mwpc_10V_9v_vmon Low voltage for MWPC station 10 ON
    3 mwpc_10V_9v_imon Low voltage for MWPC station 10 ON
    4 mwpc_10U_6v_vmon Low voltage for MWPC station 10 ON
    5 mwpc_10U_6v_imon Low voltage for MWPC station 10 ON
    6 mwpc_10U_9v_vmon Low voltage for MWPC station 10 ON
    7 mwpc_10U_9v_imon Low voltage for MWPC station 10 ON
    8 mwpc_10X_6v_vmon Low voltage for MWPC station 10 ON
    9 mwpc_10X_6v_imon Low voltage for MWPC station 10 ON
    10 mwpc_10X_9v_vmon Low voltage for MWPC station 10 ON
    11 mwpc_10X_9v_imon Low voltage for MWPC station 10 ON
    12 mwpc_9X_6v_vmon Low voltage for MWPC station 9 ON
    13 mwpc_9X_6v_imon Low voltage for MWPC station 9 ON
    14 mwpc_9X_9v_vmon Low voltage for MWPC station 9 ON
    15 mwpc_9X_9v_imon Low voltage for MWPC station 9 ON
    16 mwpc_9V_6v_vmon Low voltage for MWPC station 9 ON
    17 mwpc_9V_6v_imon Low voltage for MWPC station 9 ON
    18 mwpc_9V_9v_vmon Low voltage for MWPC station 9 ON
    19 mwpc_9V_9v_imon Low voltage for MWPC station 9 ON
    20 mwpc_9U_6v_vmon Low voltage for MWPC station 9 ON
    21 mwpc_9U_6v_imon Low voltage for MWPC station 9 ON
    22 mwpc_9U_9v_vmon Low voltage for MWPC station 9 ON
    23 mwpc_9U_9v_imon Low voltage for MWPC station 9 ON
    24 mwpc_8V_6v_vmon Low voltage for MWPC station 8 ON
    25 mwpc_8V_6v_imon Low voltage for MWPC station 8 ON
    26 mwpc_8V_9v_vmon Low voltage for MWPC station 8 ON
    27 mwpc_8V_9v_imon Low voltage for MWPC station 8 ON
    28 mwpc_8U_6v_vmon Low voltage for MWPC station 8 ON
    29 mwpc_8U_6v_imon Low voltage for MWPC station 8 ON
    30 mwpc_8U_9v_vmon Low voltage for MWPC station 8 ON
    31 mwpc_8U_9v_imon Low voltage for MWPC station 8 ON

  • ELMB #13
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack, Jura side.
    Status: installed
    Comments: ELMB #13 and ELMB #14 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    0 mwpc_6X_6v_vmon Low voltage for MWPC station 6 ON
    1 mwpc_6X_6v_imon Low voltage for MWPC station 6 ON
    2 mwpc_6X_9v_vmon Low voltage for MWPC station 6 ON
    3 mwpc_6X_9v_imon Low voltage for MWPC station 6 ON
    4 mwpc_5V_6v_vmon Low voltage for MWPC station 5 ON
    5 mwpc_5V_6v_imon Low voltage for MWPC station 5 ON
    6 mwpc_5V_9v_vmon Low voltage for MWPC station 5 ON
    7 mwpc_5V_9v_imon Low voltage for MWPC station 5 ON
    8 mwpc_2U_6v_vmon Low voltage for MWPC station 2 ON
    9 mwpc_2U_6v_imon Low voltage for MWPC station 2 ON
    10 mwpc_2U_9v_vmon Low voltage for MWPC station 2 ON
    11 mwpc_2U_9v_imon Low voltage for MWPC station 2 ON
    12 mwpc_2V_6v_vmon Low voltage for MWPC station 2 ON
    13 mwpc_2V_6v_imon Low voltage for MWPC station 2 ON
    14 mwpc_2V_9v_vmon Low voltage for MWPC station 2 ON
    15 mwpc_2V_9v_imon Low voltage for MWPC station 2 ON
    16 mwpc_2X_6v_vmon Low voltage for MWPC station 2 ON
    17 mwpc_2X_6v_imon Low voltage for MWPC station 2 ON
    18 mwpc_2X_9v_vmon Low voltage for MWPC station 2 ON
    19 mwpc_2X_9v_imon Low voltage for MWPC station 2 ON
    20 mwpc_3X_6v_vmon Low voltage for MWPC station 3 ON
    21 mwpc_3X_6v_imon Low voltage for MWPC station 3 ON
    22 mwpc_3X_9v_vmon Low voltage for MWPC station 3 ON
    23 mwpc_3X_9v_imon Low voltage for MWPC station 3 ON
    24 mwpc_3U_6v_vmon Low voltage for MWPC station 3 ON
    25 mwpc_3U_6v_imon Low voltage for MWPC station 3 ON
    26 mwpc_3U_9v_vmon Low voltage for MWPC station 3 ON
    27 mwpc_3U_9v_imon Low voltage for MWPC station 3 ON
    28 mwpc_3V_6v_vmon Low voltage for MWPC station 3 ON
    29 mwpc_3V_6v_imon Low voltage for MWPC station 3 ON
    30 mwpc_3V_9v_vmon Low voltage for MWPC station 3 ON
    31 mwpc_3V_9v_imon Low voltage for MWPC station 3 ON
    62 - 63 Mag_Sm2_T_Water_Depart Pt4w temperature sensor ON

  • ELMB #14
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack, Jura side
    Status: installed.
    Comments: ELMB #13 and ELMB #14 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    0 mwpc_4U_6v_vmon Low voltage for MWPC station 4 ON
    1 mwpc_4U_6v_imon Low voltage for MWPC station 4 ON
    2 mwpc_4U_9v_vmon Low voltage for MWPC station 4 ON
    3 mwpc_4U_9v_imon Low voltage for MWPC station 4 ON
    4 mwpc_4V_6v_vmon Low voltage for MWPC station 4 ON
    5 mwpc_4V_6v_imon Low voltage for MWPC station 4 ON
    6 mwpc_4V_9v_vmon Low voltage for MWPC station 4 ON
    7 mwpc_4V_9v_imon Low voltage for MWPC station 4 ON
    8 mwpc_4X_6v_vmon Low voltage for MWPC station 4 ON
    9 mwpc_4X_6v_imon Low voltage for MWPC station 4 ON
    10 mwpc_4X_9v_vmon Low voltage for MWPC station 4 ON
    11 mwpc_4X_9v_imon Low voltage for MWPC station 4 ON
    12 mwpc_5X_6v_vmon Low voltage for MWPC station 5 ON
    13 mwpc_5X_6v_imon Low voltage for MWPC station 5 ON
    14 mwpc_5X_9v_vmon Low voltage for MWPC station 5 ON
    15 mwpc_5X_9v_imon Low voltage for MWPC station 5 ON
    16 mwpc_5U_6v_vmon Low voltage for MWPC station 5 ON
    17 mwpc_5U_6v_imon Low voltage for MWPC station 5 ON
    18 mwpc_5U_9v_vmon Low voltage for MWPC station 5 ON
    19 mwpc_5U_9v_imon Low voltage for MWPC station 5 ON
    21 mwpc_6V_6v_vmon Low voltage for MWPC station 6 ON
    25 mwpc_6V_6v_imon Low voltage for MWPC station 6 ON
    26 mwpc_6V_9v_vmon Low voltage for MWPC station 6 ON
    27 mwpc_6V_9v_imon Low voltage for MWPC station 6 ON
    28 mwpc_6U_6v_vmon Low voltage for MWPC station 6 ON
    29 mwpc_6U_6v_imon Low voltage for MWPC station 6 ON
    30 mwpc_6U_9v_vmon Low voltage for MWPC station 6 ON
    31 mwpc_6U_9v_imon Low voltage for MWPC station 6 ON
    60 - 61 Mag_Sm2_T_Water_Return Pt4w temperature sensor ON
    62 - 63 pt4w_elmb14_T63 Pt4w temperature sensor inside hall 888, T14 ON

  • ELMB #15
    CANbus line #2
    ADC mode:unipolar; ADC range: 100 mV.
    Place: bld. 888, on gallery, Jura side
    Status: installed.
    ADC channels Dp name Comments Status
    1 mwpc_1X_6v_vmon Low voltage for MWPC station 1 ON
    2 mwpc_1X_6v_imon Low voltage for MWPC station 1 ON
    3 mwpc_1X_9v_vmon Low voltage for MWPC station 1 ON
    4 mwpc_1X_9v_imon Low voltage for MWPC station 1 ON
    5 mwpc_1Y_6v_vmon Low voltage for MWPC station 1 ON
    6 mwpc_1Y_6v_imon Low voltage for MWPC station 1 ON
    7 mwpc_1Y_9v_vmon Low voltage for MWPC station 1 ON
    8 mwpc_1Y_9v_imon Low voltage for MWPC station 1 ON
    9 mwpc_1V_6v_vmon Low voltage for MWPC station 1 ON
    10 mwpc_1V_6v_imon Low voltage for MWPC station 1 ON
    11 mwpc_1V_9v_vmon Low voltage for MWPC station 1 ON
    12 mwpc_1V_9v_imon Low voltage for MWPC station 1 ON
    13 mwpc_1U_6v_vmon Low voltage for MWPC station 1 ON
    14 mwpc_1U_6v_imon Low voltage for MWPC station 1 ON
    15 mwpc_1U_9v_vmon Low voltage for MWPC station 1 ON
    16 mwpc_1U_9v_imon Low voltage for MWPC station 1 ON
    62 - 63 pt4w-elmb15-T63 Pt4w temperature sensor inside hall 888, T10 OFF

  • ELMB #16
    CANbus line #1
    ADC mode: bipolar; ADC range: 1 V.
    Place: Trigger room HNB422
    Status: installed.
    Comments: Automated system for Gas distribution in the area provides 3 switches. A small current is injected to give the signal (closed=on=alarm). Also PS for Veto Box gives current and voltage (scaling factors applied in PVSS according to the PS info -> 1V=0.4A and 1V=3.33 KV).
    ADC channels Dp name Comments Status
    0 - 1 Temp_NIM_1 Pt4w temperature sensor, inside ELMB box OFF
    58 VBX_PS_V Voltage from Veto Box PS unit OFF
    59 VBX_PS_I Current from Veto Box PS unit OFF
    62 Gas_lv3_alarm Level 3 alarm from Gas gen. distrib. system OFF
    63 Gas_gen_alarm General alarm from Gas gen. distrib. system OFF
    64 Gas_lv2_alarm Level 2 alarm from Gas gen. distrib. system OFF

  • ELMB #17
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, STRAW frame, close to ELMB #6
    Status: spare, NO Data Points in PVSS

  • ELMB #18
    CANbus line #1
    ADC mode: bipolar; ADC range: 1 V.
    Place: Trigger room HNB429
    Status: installed.
    ADC channels Dp name Comments Status
    16 - 17 PT_4W_16_17 Pt4w temperature sensor inside trigger room ON
    18 - 19 PT_4W_18_19 Pt4w temperature sensor inside DAQ room ON
    25 Ecal1_Hv_Laser TTL signal for monitoring status of Laser for ECAL1 ON
    26 Ecal1_Lv_Gams_Voltage Low voltage of ECAL1 (GAMS), "100 V" ON
    27 Ecal1_Lv_Gams_Current Low voltage of ECAL1 (GAMS), "100 V" ON
    28 Ecal1_Lv_Mainz_Olga_Voltage Low voltage of ECAL1 (Mainz and OLGA), "100 V" ON
    29 Ecal1_Lv_Mainz_Olga_Current Low voltage of ECAL1 (Mainz and OLGA), "100 V" ON
    30 Ecal2_Lv_Voltage Low voltage of ECAL2, "100 V" ON
    31 Ecal2_Lv_Current Low voltage of ECAL2, "100 V" ON
    49 Humidity_sensor_49 Humidity sensor inside trigger room ON
    50 Humidity_sensor_50 Humidity sensor inside DAQ room ON
    51 Humidity_sensor_51 Humidity sensor inside Veto room ON
    62-63 PT_4W_62_63 Pt4w temperature sensor inside Veto room ON

  • ELMB #19
    CANbus line #1
    ADC mode: unipolar; ADC range 100 mV.
    Place: bld. 888, beam area downstream, MW2 power supply rack.
    Status: installed.
    ADC channels Dp name Comments Status
    0 Ampl X1-1 Amplifier for X1, mW2 low voltage PS ON
    1 Ampl X1-2 Amplifier for X1, mW2 low voltage PS ON
    2 Ampl V1-1 Amplifier for V1, mW2 low voltage PS ON
    3 Ampl V1-2 Amplifier for V1, mW2 low voltage PS ON
    4 Ampl X2-1 Amplifier for X2, mW2 low voltage PS ON
    5 Ampl X2-2 Amplifier for X2, mW2 low voltage PS ON
    6 Ampl V2-1 Amplifier for V2, mW2 low voltage PS ON
    7 Ampl V2-2 Amplifier for V2, mW2 low voltage PS ON
    9 Ampl Y1 mW2 low voltage PS ON
    11 Ampl Y2 mW2 low voltage PS ON
    12 TDC mW2 low voltage PS ON
    13     OFF
    14 LAX2_N2 TDC for X,V, mW2 low voltage PS ON
    15   Thresholds Y1, Y2, mW2 low voltage PS ON
    16   Thresholds X1, V1, mW2 low voltage PS ON
    17   Thresholds X2, V2, mW2 low voltage PS ON
    62 - 63 pt4w_elmb19_T63 Pt4w temperature sensor, T19 ON

  • ELMB #20
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 power supply rack.
    Status: installed.
    ADC channels Dp name Comments Status
    0 W05_1_6V voltage, low voltage PS for W45 ON
    1 W05_1_6A current, low voltage PS for W45 ON
    2 W05_1_9V voltage, low voltage PS for W45 ON
    3 W05_1_9A current, low voltage PS for W45 ON
    4 W05_2_6V voltage, low voltage PS for W45 ON
    5 W05_2_6A current, low voltage PS for W45 ON
    6 W05_2_9V voltage, low voltage PS for W45 ON
    7 W05_2_9A current, low voltage PS for W45 ON
    8 W04_1_6V voltage, low voltage PS for W45 ON
    9 W04_1_6A current, low voltage PS for W45 ON
    10 W04_1_9V voltage, low voltage PS for W45 ON
    11 W04_1_9A current, low voltage PS for W45 ON
    12 W04_2_6V voltage, low voltage PS for W45 ON
    13 W04_2_6A current, low voltage PS for W45 ON
    14 W04_2_9V voltage, low voltage PS for W45 ON
    15 W04_2_9A current, low voltage PS for W45 ON
    16 W02_1_6V voltage, low voltage PS for W45 ON
    17 W02_1_6A current, low voltage PS for W45 ON
    18 W02_1_9V voltage, low voltage PS for W45 ON
    19 W02_1_9A current, low voltage PS for W45 ON
    20 W02_2_6V voltage, low voltage PS for W45 ON
    21 W02_2_6A current, low voltage PS for W45 ON
    22 W02_2_9V voltage, low voltage PS for W45 ON
    23 W02_2_9A current, low voltage PS for W45 ON
    24 W01_1_6V voltage, low voltage PS for W45 ON
    25 W01_1_6A current, low voltage PS for W45 ON
    26 W01_1_9V voltage, low voltage PS for W45 ON
    27 W01_1_9A current, low voltage PS for W45 ON
    28 W01_2_6V voltage, low voltage PS for W45 ON
    29 W01_2_6A current, low voltage PS for W45 ON
    30 W01_2_9V voltage, low voltage PS for W45 ON
    31 W01_2_9A current, low voltage PS for W45 ON


  • ELMB #22
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Straw station 5 frame.
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 ST05V1_TDS Pt4w temp sensor, Straw station 5 ON
    2 - 3 ST05V1_TDM Pt4w temp sensor, Straw station 5 ON
    4 - 5 ST05V1_TDJ Pt4w temp sensor, Straw station 5 ON
    6 - 7 ST05V1_TMS Pt4w temp sensor, Straw station 5 ON
    8 - 9 ST05V1_TMJ Pt4w temp sensor, Straw station 5 ON
    10 - 11 ST05V1_TUS Pt4w temp sensor, Straw station 5 ON
    12 - 13 ST05V1_TUM Pt4w temp sensor, Straw station 5 ON
    14 - 15 ST05V1_TUJ Pt4w temp sensor, Straw station 5 ON
    16 - 17 ST05Y1_TDS Pt4w temp sensor, Straw station 5 ON
    18 - 19 ST05Y1_TDM Pt4w temp sensor, Straw station 5 ON
    20 - 21 ST05Y1_TDJ Pt4w temp sensor, Straw station 5 ON
    22 - 23 ST05Y1_TMS Pt4w temp sensor, Straw station 5 ON
    24 - 25 ST05Y1_TMJ Pt4w temp sensor, Straw station 5 ON
    26 - 27 ST05Y1_TUS Pt4w temp sensor, Straw station 5 ON
    28 - 29 ST05Y1_TUM Pt4w temp sensor, Straw station 5 ON
    30 - 31 ST05Y1_TUJ Pt4w temp sensor, Straw station 5 ON
    32 - 33 ST05X1_TDS Pt4w temp sensor, Straw station 5 ON
    34 - 35 ST05X1_TDM Pt4w temp sensor, Straw station 5 ON
    36 - 37 ST05X1_TDJ Pt4w temp sensor, Straw station 5 ON
    38 - 39 ST05X1_TMS Pt4w temp sensor, Straw station 5 ON
    40 - 41 ST05X1_TMJ Pt4w temp sensor, Straw station 5 ON
    42 - 43 ST05X1_TUS Pt4w temp sensor, Straw station 5 ON
    44 - 45 ST05X1_TUM Pt4w temp sensor, Straw station 5 ON
    46 - 47 ST05X1_TUJ Pt4w temp sensor, Straw station 5 ON
    48 ST05V1_H Humidity sensor, Straw station 5 ON
    49 ST05Y1_H Humidity sensor, Straw station 5 ON
    50 ST05X1_H Humidity sensor, Straw station 5 ON
    51 DL16_H Humidity sensor, Straw station 5 ON

  • ELMB #23
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 Rack.
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 W01_UP Pt4w temperature sensor ON
    2 - 3 W01_DOWN Pt4w temperature sensor ON
    4 - 5 W01_RIGHT Pt4w temperature sensor ON
    6 - 7 W01_LEFT Pt4w temperature sensor ON
    8 - 9 W02_UP Pt4w temperature sensor ON
    10 - 11 W02_DOWN Pt4w temperature sensor ON
    12 - 13 W02_LEFT Pt4w temperature sensor ON
    14 - 15 W02_RIGHT Pt4w temperature sensor ON
    16 - 17 W03_UP Pt4w temperature sensor ON
    18 - 19 W03_DOWN Pt4w temperature sensor ON
    20 - 21 W03_LEFT Pt4w temperature sensor ON
    22 - 23 W03_RIGHT Pt4w temperature sensor ON
    24 - 25 W04_UP Pt4w temperature sensor ON
    26 - 27 W04_DOWN Pt4w temperature sensor ON
    28 - 29 W04_LEFT Pt4w temperature sensor ON
    30 - 31 W04_RIGHT Pt4w temperature sensor ON
    32 - 33 W05_UP Pt4w temperature sensor ON
    34 - 35 W05_DOWN Pt4w temperature sensor ON
    36 - 37 W05_LEFT Pt4w temperature sensor ON
    38 - 39 W05_RIGHT Pt4w temperature sensor ON
    40 - 41 W06_UP Pt4w temperature sensor ON
    42 - 43 W06_DOWN Pt4w temperature sensor ON
    44 - 45 W06_LEFT Pt4w temperature sensor ON
    46 - 47 W06_RIGHT Pt4w temperature sensor ON
    48 - 49 W05_UP Pt4w temperature sensor ON
    50 - 51 T_Concrete Pt4w temperature sensor, T23 ON

  • ELMB #24
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Gallery.
    Status: installed.
    ADC channels Dp name Comments Status
    2 - 3   Pt4w temperature sensor OFF
    6 - 7   Pt4w temperature sensor OFF
    14 - 15 Env_T_Gallery Pt4w temperature sensor, T24 ON

  • ELMB #25
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, RICH rack, Saleve side.
    Status: installed, but not connected to RICH, not integrated in PVSS

  • ELMB #29
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Straw frame, Jura side.
    Comments:
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 ST02V2_TDS_up Pt4w temperature sensor ON
    2 - 3 ST02V2_TDM_up Pt4w temperature sensor ON
    4 - 5 ST02V2_TDJ_up Pt4w temperature sensor ON
    6 - 7 ST02V2_TMS_up Pt4w temperature sensor ON
    8 - 9 ST02V2_TMJ_up Pt4w temperature sensor ON
    10 - 11 ST02V2_TUS_up Pt4w temperature sensor ON
    12 - 13 ST02V2_TUM_up Pt4w temperature sensor ON
    14 - 15 ST02V2_TUJ_up Pt4w temperature sensor ON
    16 - 17 ST02Y2_TDS_up Pt4w temperature sensor ON
    18 - 19 ST02Y2_TDM_up Pt4w temperature sensor ON
    20 - 21 ST02Y2_TDJ_up Pt4w temperature sensor OFF
    22 - 23 ST02Y2_TMS_up Pt4w temperature sensor ON
    24 - 25 ST02Y2_TMJ_up Pt4w temperature sensor ON
    26 - 27 ST02Y2_TUS_up Pt4w temperature sensor ON
    28 - 29 ST02Y2_TUM_up Pt4w temperature sensor ON
    30 - 31 ST02Y2_TUJ_up Pt4w temperature sensor ON
    32 - 33 ST02X2_TDS_up Pt4w temperature sensor ON
    34 - 35 ST02X2_TDM_up Pt4w temperature sensor ON
    36 - 37 ST02X2_TDJ_up Pt4w temperature sensor ON
    38 - 39 ST02X2_TMS_up Pt4w temperature sensor ON
    40 - 41 ST02X2_TMJ_up Pt4w temperature sensor ON
    42 - 43 ST02X2_TUS_up Pt4w temperature sensor OFF
    44 - 45 ST02X2_TUM_up Pt4w temperature sensor ON
    46 - 47 ST02X2_TUJ_up Pt4w temperature sensor ON
    48 ST02V2_H_up Humidity sensor OFF
    49 ST02X2_H_up Humidity sensor OFF
    50 ST02Y2_H_up Humidity sensor OFF
    51 ST02X1_H_up Humidity sensor OFF
    52 ST02U1_H_up Humidity sensor OFF
    53 ST02Y1_H_up Humidity sensor OFF
  • ELMB #30
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Straw frame, Jura side.
    Comments:
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 ST02V2_TDS_down Pt4w temperature sensor ON
    2 - 3 ST02V2_TDM_down Pt4w temperature sensor ON
    4 - 5 ST02V2_TDJ_down Pt4w temperature sensor OFF
    6 - 7 ST02V2_TMS_down Pt4w temperature sensor ON
    8 - 9 ST02V2_TMJ_down Pt4w temperature sensor ON
    10 - 11 ST02V2_TUS_down Pt4w temperature sensor ON
    12 - 13 ST02V2_TUM_down Pt4w temperature sensor ON
    14 - 15 ST02V2_TUJ_down Pt4w temperature sensor ON
    16 - 17 ST02Y2_TDS_down Pt4w temperature sensor ON
    18 - 19 ST02Y2_TDM_down Pt4w temperature sensor ON
    20 - 21 ST02Y2_TDJ_down Pt4w temperature sensor ON
    22 - 23 ST02Y2_TMS_down Pt4w temperature sensor OFF
    24 - 25 ST02Y2_TMJ_down Pt4w temperature sensor ON
    26 - 27 ST02Y2_TUS_down Pt4w temperature sensor OFF
    28 - 29 ST02Y2_TUM_down Pt4w temperature sensor ON
    30 - 31 ST02Y2_TUJ_down Pt4w temperature sensor ON
    32 - 33 ST02X2_TDS_down Pt4w temperature sensor ON
    34 - 35 ST02X2_TDM_down Pt4w temperature sensor ON
    36 - 37 ST02X2_TDJ_down Pt4w temperature sensor ON
    38 - 39 ST02X2_TMS_down Pt4w temperature sensor ON
    40 - 41 ST02X2_TMJ_down Pt4w temperature sensor ON
    42 - 43 ST02X2_TUS_down Pt4w temperature sensor ON
    44 - 45 ST02X2_TUM_down Pt4w temperature sensor ON
    46 - 47 ST02X2_TUJ_down Pt4w temperature sensor ON
    48 ST02V2_H_down Humidity sensor OFF
    49 ST02X2_H_down Humidity sensor OFF
    50 ST02Y2_H_down Humidity sensor OFF
    51 ST02X1_H_down Humidity sensor OFF
    52 ST02U1_H_down Humidity sensor OFF
    53 ST02Y1_H_down Humidity sensor OFF
  • ELMB #31
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, DC4, Jura side.
    Comments:
    Status: installed.
    ADC channels Dp name Comments Status
    0 - 1 TT01 Pt4w temperature sensor ON
    2 - 3 TT02 Pt4w temperature sensor ON
    4 - 5 TT03 Pt4w temperature sensor ON
    6 - 7 TT04 Pt4w temperature sensor ON
    8 - 9 TT05 Pt4w temperature sensor ON
    10 - 11 TT06 Pt4w temperature sensor ON
    12 - 13 TT07 Pt4w temperature sensor ON
    14 - 15 TT08 Pt4w temperature sensor ON
    16 - 17 TT16 Pt4w temperature sensor ON
    18 - 19 TT09 Pt4w temperature sensor ON
    20 - 21 TT10 Pt4w temperature sensor ON
    22 - 23 TT11 Pt4w temperature sensor ON
    24 - 25 TT12 Pt4w temperature sensor ON
    26 - 27 TT13 Pt4w temperature sensor ON
    28 - 29 TT14 Pt4w temperature sensor ON
    30 - 31 TT15 Pt4w temperature sensor ON
    32 - 33 TT20 Pt4w temperature sensor ON
    34 - 35 TT21 Pt4w temperature sensor ON
    36 - 37 TT22 Pt4w temperature sensor ON
    38 - 39 TT23 Pt4w temperature sensor ON
    40 - 41 TT24 Pt4w temperature sensor ON
    42 - 43 TT25 Pt4w temperature sensor ON
    44 - 45 TT26 Pt4w temperature sensor ON
    46 - 47 TT27 Pt4w temperature sensor ON
    54 - 55 Mag_Sm1_T_Water_Return Pt4w temperature sensor ON
    56 - 57 Mag_Sm1_T_Water_Depart Pt4w temperature sensor ON
    58 - 59 T_Raw_Water_Return Pt4w temperature sensor ON
    60 - 61 T_Air_Duct_DC_MM Pt4w temperature sensor ON
    62 - 63 T_Raw_Water_Depart Pt4w temperature sensor ON
  • ELMB #32
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 Rack, Saleve side.
    Comments: ELMB used for monitoring of ECAL2 LV.
    Status: installed.
    ADC channels Dp name Comments Status
    0 Ecal2_Lv_C0 ECAL2 LV distributor, column 0 ON
    1 Ecal2_Lv_C1 ECAL2 LV distributor, column 1 ON
    2 Ecal2_Lv_C2 ECAL2 LV distributor, column 2 ON
    3 Ecal2_Lv_C3 ECAL2 LV distributor, column 3 ON
    4 Ecal2_Lv_C4 ECAL2 LV distributor, column 4 ON
    5 Ecal2_Lv_C5 ECAL2 LV distributor, column 5 ON
    6 Ecal2_Lv_C6 ECAL2 LV distributor, column 6 ON
    7 Ecal2_Lv_C7 ECAL2 LV distributor, column 7 ON
    8 Ecal2_Lv_C8 ECAL2 LV distributor, column 8 ON
    9 Ecal2_Lv_C9 ECAL2 LV distributor, column 9 ON
    10 Ecal2_Lv_Col10 ECAL2 LV distributor, column 10 ON
    11 Ecal2_Lv_Col11 ECAL2 LV distributor, column 11 ON
    12 Ecal2_Lv_Col12 ECAL2 LV distributor, column 12 ON
    13 Ecal2_Lv_Col13 ECAL2 LV distributor, column 13 ON
    14 Ecal2_Lv_Col14 ECAL2 LV distributor, column 14 ON
    15 Ecal2_Lv_Col15 ECAL2 LV distributor, column15 ON
    27 Ecal2_Lv_for_LED_Neg_Top Low voltage of ECAL2 LED system ON
    28 Ecal2_Lv_for_LED_Neg_Bot Low voltage of ECAL2 LED system ON
    29 Ecal2_Lv_for_LED_Pos Low voltage of ECAL2 LED system ON
    30 Ecal2_Lv_for_Hv_2 Low voltage of ECAL2 for HV, "6 V" ON
    31 Ecal2_Lv_for_Hv_1 Low voltage of ECAL2 for HV, "6 V" ON
    32 Ecal2_Lv_Col16 ECAL2 LV distributor, column 16 ON
    33 Ecal2_Lv_Col17 ECAL2 LV distributor, column 17 ON
    34 Ecal2_Lv_C18 ECAL2 LV distributor, column 18 ON
    35 Ecal2_Lv_C19 ECAL2 LV distributor, column 19 ON
    36 Ecal2_Lv_C20 ECAL2 LV distributor, column 20 ON
    37 Ecal2_Lv_Col21 ECAL2 LV distributor, column 21 ON
    38 Ecal2_Lv_Col22 ECAL2 LV distributor, column 22 ON
    39 Ecal2_Lv_Col23 ECAL2 LV distributor, column 23 ON
    40 Ecal2_Lv_Col24 ECAL2 LV distributor, column 24 ON
    41 Ecal2_Lv_Col25 ECAL2 LV distributor, column 25 ON
    42 Ecal2_Lv_Col26 ECAL2 LV distributor, column 26 ON
    43 Ecal2_Lv_Col27 ECAL2 LV distributor, column 27 ON
    44 Ecal2_Lv_Col28 ECAL2 LV distributor, column 28 ON
    45 Ecal2_Lv_Col29 ECAL2 LV distributor, column 29 ON
    46 Ecal2_Lv_Col30 ECAL2 LV distributor, column 30 ON
    47 Ecal2_Lv_Col31 ECAL2 LV distributor, column 31 ON
    62 - 63 pt4w_elmb32_T63 Pt4w temperature sensor, T32 ON
  • ELMB #33
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 rack, Saleve side.
    Comments:ELMB used for monitoring of ECAL2 LV.
    Status: installed.
    ADC channels Dp name Comments Status
    32 Ecal2_Lv_Col48 ECAL2 LV distributor, column 48 ON
    33 Ecal2_Lv_Col49 ECAL2 LV distributor, column 49 ON
    34 Ecal2_Lv_Col50 ECAL2 LV distributor, column 50 ON
    35 Ecal2_Lv_Col51 ECAL2 LV distributor, column 51 ON
    36 Ecal2_Lv_Col48 ECAL2 LV distributor, column 52 ON
    37 Ecal2_Lv_Col53 ECAL2 LV distributor, column 53 ON
    38 Ecal2_Lv_Col54 ECAL2 LV distributor, column 54 ON
    39 Ecal2_Lv_Col55 ECAL2 LV distributor, column 55 ON
    40 Ecal2_Lv_Col56 ECAL2 LV distributor, column 56 ON
    41 Ecal2_Lv_Col57 ECAL2 LV distributor, column 57 ON
    42 Ecal2_Lv_Col58 ECAL2 LV distributor, column 58 ON
    43 Ecal2_Lv_Col59 ECAL2 LV distributor, column 59 ON
    44 Ecal2_Lv_Col60 ECAL2 LV distributor, column 60 ON
    45 Ecal2_Lv_Col61 ECAL2 LV distributor, column 61 ON
    46 Ecal2_Lv_Col62 ECAL2 LV distributor, column 62 ON
    47 Ecal2_Lv_Col48 ECAL2 LV distributor, column 63 ON
    32 Ecal2_Lv_Col48 ECAL2 LV distributor, column 48 ON
    33 Ecal2_Lv_Col49 ECAL2 LV distributor, column 49 ON
    34 Ecal2_Lv_Col50 ECAL2 LV distributor, column 50 ON
    35 Ecal2_Lv_Col51 ECAL2 LV distributor, column 51 ON
    36 Ecal2_Lv_Col52 ECAL2 LV distributor, column 52 ON
    37 Ecal2_Lv_Col53 ECAL2 LV distributor, column 53 ON
    38 Ecal2_Lv_Col54 ECAL2 LV distributor, column 54 ON
    39 Ecal2_Lv_Col55 ECAL2 LV distributor, column 55 ON
    40 Ecal2_Lv_Col56 ECAL2 LV distributor, column 56 ON
    41 Ecal2_Lv_Col57 ECAL2 LV distributor, column 57 ON
    42 Ecal2_Lv_Col58 ECAL2 LV distributor, column 58 ON
    43 Ecal2_Lv_Col59 ECAL2 LV distributor, column 59 ON
    44 Ecal2_Lv_Col60 ECAL2 LV distributor, column 60 ON
    45 Ecal2_Lv_Col61 ECAL2 LV distributor, column 61 ON
    46 Ecal2_Lv_Col62 ECAL2 LV distributor, column 62 ON
    47 Ecal2_Lv_Col63 ECAL2 LV distributor, column 63 ON
  • ELMB #34
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 rack, Saleve side.
    Comments: ELMB prepared for monitoring of ECAL2 LV, but not connected to the detector.
    Status: installed.
  • ELMB #35
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 rack, Saleve side.
    Comments: ELMB prepared for monitoring of ECAL2 LV, but not connected to the detector.
    Status: installed.

Last update: August 9th, 2016