   28 ELMBs are connected to 3 CANbus lines with total length of approx 400 m. ELMBs on CANbus lines 1 and 2 are of old type, while ELMBs on CANbus line 3 are new type. To avoid cross-talk between different detectors and their electronics, it was decided to have independent ELMBs for each detectors or sub-system, whenever possible. The distribution of the ELMBs over the experimental hall is optimized in order to have the shortest wiring connections to sensors or monitoring points.

   The monitoring is done using CANOpen OPC Server (CanOpc.exe), running on na58pc014 PC(Windows 2000), installed in DCS room HNB423. The configuration file for the OPC Server is located in the "OPC" directory. A PVSS API manager "PVSS00opc -num 1", as a client, connects to the OPCCanOpen Server. 3 ports of a Kvaser PCI-CAN Q (4 ports) interface card are used (the card is in 4 indepent ports configuration). The CANbus network consists of 3 CANbus branches, of 120 m, 210 m and 50m lenght. Due to their long length (>50 m), cable with 6 conducting wires with cross-section 0.5 mm2 for each is used for CANbus1 and CANbus2 (multiconductor screened cable layer twisted, CERN catalogue - 04.21.51.106.0), and cable with 8 conducting wires for CANbus3.

   A special transition board is used for the ELMB connection to the network cable (see the scheme here). The wires of thick cable are ended by pins and screws on board contacts, which has printed wiring between to Dsub 9 pin connector. The ELMB CANbus connector connects to the transition board via a short(0,5 m) flat cable.

   Each ELMB has its own local power supply and there is only one central power supply for the CANbus. The system has full optocoupling between nodes connected to CANbus line. The power supply for the CANbus provides 12V and a current of 1.5-2 Amps, being located in the DCS room, close to the na58pc014 PC. This powers the CANbus receivers/transmitters, which are optically insulated from the ELMB internal circuit. The ELMBs have their own local power supplies. As a rule, each ELMB has a power supply for its analog part and another for the digital part. In some cases one common power supply is used for both parts. The nominal voltage of the power supplies is 12V. There are 2 types of power supplies used as local: Switching power supply OMRON model S82K with 12V output, Imax=1.5A (mounted in a rail and with protection cover); and Regulated Adapter type EP2, FRIWO with output 12V, Imax=0.5A.

   Plugged to the ELMB's motherboard, 2 types of adapters are used, depending of the input signals to the ELMB: High performance Pt100 adapters, with Rc = 3.9 KOhm, Rs = 100 Ohm (to be used with Pt4w temperature sensors); and Differential attenuators with 1:100 divider (100 KOhm/1 KOhm).

   Different kinds of sensors are used, depending on the parameters to be monitored. For temperature measurements we use Pt100 sensors. The humidity measurements are done using type HIH 3605A humidity sensors. For pressure measurements, type 144S PCB Series is used. The magnetic field is measured with UGN35 Hall probe.

   In PVSS, there are several monitoring parameters with associated alarm signals defined (so that an alarm will be displayed if the read value goes out of a given min/max threshold). The alarm causes changing the background colour of the alarm text window, from green to red, orange or yellow. Also, the alarm signal will be propagated to the top of the monitoring system hierarchy and cause changing the colour of the ELMB_A button on the main COMPASS control panel.

   The monitoring parameters, that can produce alarm signals are:

  1. T_W_DEP; T_W_RET. These 2 parameters represent the temperatures of incoming and outgoing water in the RICH electronics cooling system.

  2. SM1_M_F. Measurement of the stability of SM1 magnetic field.

  3. B6_M_F. Measurement of the stability of B6 magnetic field.

  4. PT_1_HSO; PT_2_DTF ; PT_3_SLT; PT_4_MHG; PT_5_SCW; PT_6_SFC; PT_7_NMR; PT_8_SCL. These 8 parameters represent the temperatures of different points in the Polarized Target platform.

  5. mW2_gas_alarm. This parameter represents the status of gas system for mW2 detector.

  6. The following 16 parameters represent the temperatures of different points on electronics readout boards of SILICON detectors:
    SI02_T_u1; SI01_T_u1; SI02_T_u2; SI01_T_u2; SI02_T_v1; SI01_T_v1 (sensor on SI03); SI02_T_v2; SI01_T_v2 (sensor on SI03); SI02_T_y1; SI01_T_y1; SI02_T_y2; SI01_T_y2; SI02_T_x1; SI01_T_x1 (sensor on SI03); SI02_T_x2; SI01_T_x2 (sensor on SI03).


ELMBs configuration

Jump to ELMB #:
1    2    3    4    5    6    7    8    9    10    11    12    13
14    15    16    17    18    19    20    21    22    23    24    25    26    27    28   

  • ELMB #1
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: HNB 425, DAQ room, temperature measurements.
    Status: installed.
    ADC channels Dp name Comments Status
    33 - 34 T_RB_1 Temperature inside Readout Buffer Rack 1 ON
    35 - 36 T_RB_2 Temperature inside Readout Buffer Rack 2 ON
    37 - 38 T_EB_1 Temperature inside Event Builder Rack 1 ON
    39 - 40 T_EB_2 Temperature inside Event Builder Rack 2 ON

  • ELMB #2
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: MW1 FE LV power supply rack, SM2 region, Jura side.
    Status: installed.
    Comments: Cable entering ELMB channels 0-15 labelled "ADC input 1"; to channels 16-31 labelled "ADC input 3"; to channels 32-47 labelled "ADC input 2". In PVSS the factors 0.6, 1.4 and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
    ADC channels Dp name Comments Status
    1 mW1_C31_5Vp Crate #3, +5V, channel 1 ON
    2 mW1_C31_5Vn Crate #3, -5V, channel 1 ON
    3 mW1_C32_5Vp Crate #3, +5V, channel 2 ON
    4 mW1_C32_5Vn Crate #3, -5V, channel 2 ON
    5 mW1_C41_5Vp Crate #4, +5V, channel 1 ON
    6 mW1_C41_5Vn Crate #4, -5V, channel 1 ON
    7 mW1_C42_5Vp Crate #4, +5V, channel 2 ON
    8 mW1_C42_5Vn Crate #4, -5V, channel 2 ON
    9 mW1_C51_5Vp Crate #5, +5V, channel 1 ON
    10 mW1_C51_5Vn Crate #5, -5V, channel 1 ON
    11 mW1_C52_5Vp Crate #5, +5V, channel 2 ON
    12 mW1_C52_5Vn Crate #5, -5V, channel 2 ON
    17 mW1_V3_5Vp Crate VME #3, +5V voltage ON
    18 mW1_V3_5Ip Crate VME #3, +5V current ON
    19 mW1_V3_12Vp Crate VME #3, +12V voltage ON
    20 mW1_V3_12Ip Crate VME #3, +12V current ON
    21 mW1_V3_12Vn Crate VME #3, -12V voltage ON
    22 mW1_V3_12In Crate VME #3, -12V current ON
    23 mW1_V3_OVT Crate VME #3 PS Over-Temperature ON
    24 mW1_V3_OLD Crate VME #3 cards Over-Temperature ON
    33 mW1_V1_5Vp Crate VME #1, +5V voltage ON
    34 mW1_V1_5Ip Crate VME #1, +5V current ON
    35 mW1_V1_12Vp Crate VME #1, +12V voltage ON
    36 mW1_V1_12Ip Crate VME #1, +12V current ON
    37 mW1_V1_12Vn Crate VME #1, -12V voltage ON
    38 mW1_V1_12In Crate VME #1, -12V current ON
    39 mW1_V1_OVT Crate VME #1 PS Over-Temperature ON
    40 mW1_V1_OLD Crate VME #1 cards Over-Temperature ON
    41 mW1_V2_5Vp Crate VME #2, +5V voltage ON
    42 mW1_V2_5Ip Crate VME #2, +5V current ON
    43 mW1_V2_12Vp Crate VME #2, +12V voltage ON
    44 mW1_V2_12Ip Crate VME #2, +12V current ON
    45 mW1_V2_12Vn Crate VME #2, -12V voltage ON
    46 mW1_V2_12In Crate VME #2, -12V current ON
    47 mW1_V2_OVT Crate VME #2 PS Over-Temperature ON
    48 mW1_V2_OLD Crate VME #2 cards Over-Temperature ON
    63 - 64 pt4w_elmb2_T64 Pt4w temperature sensor, T11 ON

  • ELMB #3
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: BMS electronics room.
    Status: installed.
    ADC channels Dp name Comments Status
    1 bmse_lv_1p NIM crate #1, +6V OFF
    2 bmse_lv_2p NIM crate #2, +6V OFF
    3 bmse_lv_3p NIM crate #3, +6V OFF
    4 bmse_lv_4p NIM crate #4, +6V OFF
    5 bmse_lv_1n NIM crate #1, -6V OFF
    6 bmse_lv_2n NIM crate #2, -6V OFF
    7 bmse_lv_3n NIM crate #3, -6V OFF
    8 bmse_lv_4n NIM crate #4, -6V OFF
    33 mW2_gas_alarm Gas alarm from MW2 gas system ON
    34 mW1_gas_alarm Gas alarm from MW1 gas system OFF
    35 mW1_gas_argon Argon gas flow value in MW1 OFF
    36 mW1_gas_co2 CO2 gas flow value in MW1 OFF
    37 ecal2_hv_signal HV system alarm for ECAL2 ON
    61 - 62 T_W_RET Pt4w temp sensor, incoming water for RICH electronics cooling ON
    63 - 64 T_W_DEP Pt4w temp sensor, outgoing water from RICH electronics cooling ON

  • ELMB #4
    CANbus line #2
    ADC mode: unipolar; ADC range: 1 V.
    Place: MW1 FE LV power supply rack, SM2 region, Saleve side.
    Status: installed.
    Comments: In PVSS the factors 0.6, 1.4 and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
    ADC channels Dp name Comments Status
    1 mW1_C11_5p Crate #1, +5V, channel 1 ON
    2 mW1_C11_5n Crate #1, -5V, channel 1 ON
    3 mW1_C12_5p Crate #1, +5V, channel 2 ON
    4 mW1_C12_5n Crate #1, -5V, channel 2 ON
    5 mW1_C21_5p Crate #2, +5V, channel 1 ON
    6 mW1_C21_5n Crate #2, -5V, channel 1 ON
    7 mW1_C22_5p Crate #2, +5V, channel 2 ON
    8 mW1_C22_5n Crate #2, -5V, channel 2 ON
    17 mW1_V4_5Vp Crate VME #4, +5V voltage ON
    18 mW1_V4_5Ip Crate VME #4, +5V current ON
    19 mW1_V4_12Vp Crate VME #4, +12V voltage ON
    20 mW1_V4_12Ip Crate VME #4, +12V current ON
    21 mW1_V4_12Vn Crate VME #4, -12V voltage ON
    22 mW1_V4_12In Crate VME #4, -12V current ON
    23 mW1_V4_OVT Crate VME #4 PS Over-Temperature ON
    24 mW1_V4_OLD Crate VME #4 cards Over-Temperature ON
    25 mW1_V5_5Vp Crate VME #5, +5V voltage ON
    26 mW1_V5_5Ip Crate VME #5, +5V current ON
    27 mW1_V5_12Vp Crate VME #5, +12V voltage ON
    28 mW1_V5_12Ip Crate VME #5, +12V current ON
    29 mW1_V5_12Vn Crate VME #5, -12V voltage ON
    30 mW1_V5_12In Crate VME #5, -12V current ON
    31 mW1_V5_OVT Crate VME #5 PS Over-Temperature ON
    32 mW1_V5_OLD Crate VME #5 cards Over-Temperature ON
    63 - 64 pt4w_elmb4_T64 Pt4w temperature sensor, T5 OFF

  • ELMB #5
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: SciFiG FE LV power supply rack, SM2 region, Jura side.
    Status: installed
    ADC channels Dp name Comments Status
    1 t1 2 wire conn, temp. electronic board OFF
    2 t2 2 wire conn, temp. electronic board OFF
    3 t3 2 wire conn, temp. electronic board OFF
    4 t4 2 wire conn, temp. electronic board OFF
    5 t5 2 wire conn, temp. electronic board OFF
    6 t6 2 wire conn, temp. electronic board OFF
    7 t7 2 wire conn, temp. electronic board OFF
    8 t8 2 wire conn, temp. electronic board OFF
    9 t9 2 wire conn, temp. electronic board OFF
    10 t10 2 wire conn, temp. electronic board OFF
    11 t11 2 wire conn, temp. electronic board OFF
    12 t12 2 wire conn, temp. electronic board OFF
    13 t13 2 wire conn, temp. electronic board OFF
    14 t14 2 wire conn, temp. electronic board OFF
    15 t15 2 wire conn, temp. electronic board OFF
    16 t16 2 wire conn, temp. electronic board OFF
    57 SM2_M_F Hall probe #1 inside magnet SM2 OFF
    58 SM22_M_F Hall probe #2 inside magnet SM2 OFF
    63 - 64 pt4w_elmb5_T64 Temperature inside hall 888, T6 ON

  • ELMB #6
    CANbus line #2
    ADC mode: unipolar; ADC range: 100mV.
    Place: STRAW frame, temperature and humidity sensors, Jura side.
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 STO3V2_TDS Pt4w temperature sensor ON
    3 - 4 STO3V2_TDM Pt4w temperature sensor ON
    5 - 6 STO3V2_TDJ Pt4w temperature sensor ON
    7 - 8 STO3V2_TMS Pt4w temperature sensor ON
    9 - 10 STO3V2_TMJ Pt4w temperature sensor ON
    11 - 12 STO3V2_TUS Pt4w temperature sensor ON
    13 - 14 STO3V2_TUM Pt4w temperature sensor ON
    15 - 16 STO3V2_TUJ Pt4w temperature sensor ON
    17 - 18 STO3Y2_TDS Pt4w temperature sensor ON
    19 - 20 STO3Y2_TDM Pt4w temperature sensor ON
    21 - 22 STO3Y2_TDJ Pt4w temperature sensor ON
    23 - 24 STO3Y2_TMS Pt4w temperature sensor ON
    25 - 26 STO3Y2_TMJ Pt4w temperature sensor ON
    27 - 28 STO3Y2_TUS Pt4w temperature sensor ON
    29 - 30 STO3Y2_TUM Pt4w temperature sensor ON
    31 - 32 STO3Y2_TUJ Pt4w temperature sensor ON
    33 - 34 STO3X2_TDS Pt4w temperature sensor ON
    35 - 36 STO3X2_TDM Pt4w temperature sensor ON
    37 - 38 STO3X2_TDJ Pt4w temperature sensor ON
    39 - 40 STO3X2_TMS Pt4w temperature sensor ON
    41 - 42 STO3X2_TMJ Pt4w temperature sensor ON
    43 - 44 STO3X2_TUS Pt4w temperature sensor ON
    45 - 46 STO3X2_TUM Pt4w temperature sensor ON
    47 - 48 STO3X2_TUJ Pt4w temperature sensor ON
    49 STO3V2_H Humidity sensor ON
    50 STO3X2_H Humidity sensor ON
    51 STO3Y2_H Humidity sensor ON
    52 STO3X1_H Humidity sensor ON
    53 STO3U1_H Humidity sensor ON
    54 STO3Y1_H Humidity sensor ON

  • ELMB #7
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: RICH rack, temperature sensors inside vessel, Saleve side.
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 pt4w-RICH-1 Pt4w temperature sensor inside vessel OFF
    3 - 4 pt4w-RICH-2 Pt4w temperature sensor inside vessel OFF
    5 - 6 pt4w-RICH-3 Pt4w temperature sensor inside vessel ON
    7 - 8 pt4w-RICH-4 Pt4w temperature sensor inside vessel ON
    9 - 10 -pt4w-RICH-5 Pt4w temperature sensor inside vessel ON
    11 - 12 pt4w-RICH-6 Pt4w temperature sensor inside vessel ON
    13 - 14 pt4w-RICH-7 Pt4w temperature sensor inside vessel ON
    15 - 16 pt4w-RICH-8 Pt4w temperature sensor inside vessel ON
    17 - 18 pt4w-RICH-9 Pt4w temperature sensor inside vessel ON
    19 - 20 pt4w-RICH-10 Pt4w temperature sensor inside vessel ON
    21 - 22 pt4w-RICH-11 Pt4w temperature sensor inside vessel ON
    23 - 24 pt4w-RICH-12 Pt4w temperature sensor inside vessel ON
    25 - 26 pt4w-RICH-13 Pt4w temperature sensor inside vessel ON
    27 - 28 pt4w-RICH-14 Pt4w temperature sensor inside vessel ON
    29 - 30 pt4w-RICH-15 Pt4w temperature sensor inside vessel ON
    31 - 32 pt4w-RICH-16 Pt4w temperature sensor inside vessel ON
    33 - 34 pt4w-RICH-17 Pt4w temperature sensor inside vessel ON
    35 - 36 pt4w-RICH-18 Pt4w temperature sensor inside vessel ON
    37 - 38 pt4w-RICH-19 Pt4w temperature sensor inside vessel OFF
    39 - 40 pt4w-RICH-20 Pt4w temperature sensor inside vessel OFF
    41 - 42 pt4w-RICH-21 Pt4w temperature sensor inside vessel OFF
    43 - 44 pt4w-RICH-22 Pt4w temperature sensor inside vessel OFF
    45 - 46 pt4w-RICH-23 Pt4w temperature sensor inside vessel OFF
    47 - 48 pt4w-RICH-24 Pt4w temperature sensor inside vessel OFF
    49 - 50 pt4w-RICH-25 Pt4w temperature sensor inside vessel OFF
    51 - 52 pt4w-RICH-26 Pt4w temperature sensor inside vessel OFF
    53 - 54 pt4w-RICH-27 Pt4w temperature sensor inside vessel OFF
    55 - 56 pt4w-RICH-28 Pt4w temperature sensor inside vessel OFF
    57 - 58 pt4w-RICH-29 Pt4w temperature sensor inside vessel OFF
    59 - 60 pt4w-RICH-30 Pt4w temperature sensor inside vessel OFF
    61 - 62 pt4w-RICH-31 Pt4w temperature sensor inside vessel(?) ON
    63 - 64 pt4w-elmb7-T64 Pt4w sensor: temperature inside hall 888, T3 ON

  • ELMB #8
    CANbus line #2
    ADC mode: bipolar; ADC range: 100 mV.
    Place: SciFi rack, Saleve side.
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 PT_1_HSO Pt4w temp sensor, Pol Target horizontal screen outlet ON
    3 - 4 PT_2_DTF Pt4w temp sensor, Pol Target dilution cryostat top flange ON
    5 - 6 PT_3_SLT Pt4w temp sensor, Pol Target still line top ON
    7 - 8 PT_4_MHG Pt4w temp sensor, Pol Target magnet gas outlet ON
    9 - 10 PT_5_SCW Pt4w temp sensor, Pol Target dipole current leads ON
    11 - 12 PT_6_SFC Pt4w temp sensor, Pol Target separator flow control ON
    13 - 14 PT_7_NMR Pt4w temp sensor, Pol Target NMR rack ON
    15 - 16 PT_8_SCL Pt4w temp sensor, Pol Target solenoid current leads ON
    17 SM1_M_F Hall probe for SM1 Magnetic field ON
    21 Solenoid_Curr current for Pol Target Solenoid ON
    23 Dipole_Curr current for Pol Target Dipole magnet ON
    31 - 32 pt4w-elmb8-T64 Pt4w temperature sensor in the hall, T1 OFF
    33 - 34 SI01_T_u1 Pt4w temp sensor, SILICON station 01 ON
    35 - 36 SI01_T_u2 Pt4w temp sensor, SILICON station 01 ON
    37 - 38 SI01_T_v1 Pt4w temp sensor, temporarily on SI02_u1 ON
    39 - 40 SI01_T_v2 Pt4w temp sensor, temporarily on SI02_u2 ON
    41 - 42 SI01_T_y1 Pt4w temp sensor, temporarily on SI02_x1 ON
    43 - 44 SI01_T_y2 Pt4w temp sensor, temporarily on SI02_x2 ON
    45 - 46 SI01_T_x1 Pt4w temp sensor, SILICON station 01 ON
    47 - 48 SI01_T_x2 Pt4w temp sensor, SILICON station 01 ON
    49 - 50 SI02_T_u1 Pt4w temp sensor, temporarily on SI05_u1 ON
    51 - 52 SI02_T_u2 Pt4w temp sensor, temporarily on SI05_u2 ON
    53 - 54 SI02_T_v1 Pt4w temp sensor, temporarily on SI05_v1 OFF
    55 - 56 SI02_T_v2 Pt4w temp sensor, temporarily on SI05_v2 OFF
    57 - 58 SI02_T_y1 Pt4w temp sensor, temporarily on SI05_y1 ON
    59 - 60 SI02_T_y2 Pt4w temp sensor, temporarily on SI05_y2 ON
    61 - 62 SI02_T_x1 Pt4w temp sensor, temporarily on SI05_x1 ON
    63 - 64 SI02_T_x2 Pt4w temp sensor, temporarily on SI05_x2 ON

  • ELMB #9
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: BMS HV room HNB 202.
    Status: installed.
    ADC channels Dp name Comments Status
    1 bmsh_lv_1 Low voltage for amplifier BMS station OFF
    2 bmsh_lv_2 Low voltage for amplifier BMS station OFF
    3 bmsh_lv_3 Low voltage for amplifier BMS station OFF
    4 bmsh_lv_4 Low voltage for amplifier BMS station OFF
    5 bmsh_lv_5 Low voltage for amplifier BMS station OFF
    6 bmsh_lv_6 Low voltage for amplifier BMS station OFF
    7 bmsh_lv_7 Low voltage for amplifier BMS station OFF
    8 bmsh_lv_8 Low voltage for amplifier BMS station OFF
    9 bmsh_lv_9 Low voltage for amplifier BMS station OFF
    10 bmsh_lv_10 Low voltage for amplifier BMS station OFF
    11 bmsh_lv_11 Low voltage for amplifier BMS station OFF
    12 bmsh_lv_12 Low voltage for amplifier BMS station OFF
    43 B6_M_F sensor on Bending Magnet B6 ON
    61 - 62 AirTemp Pt4w sensor, Air temperature outside building 888 ON
    63 - 64 T_OUT_SIDE Pt4w sensor, temperature inside BMS room ON

  • ELMB #10
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, mMegas/Drifts electronics rack
    Status: installed
    ADC channels Dp name Comments Status
    1 - 2 MM03_UV_1 Pt4w temperature sensor for MM ON
    3 - 4 MM03_UV_2 Pt4w temperature sensor for MM ON
    5 - 6 MM03_UV_3 Pt4w temperature sensor for MM ON
    7 - 8 MM03_UV_4 Pt4w temperature sensor for MM ON
    9 - 10 MM03_XY_1 Pt4w temperature sensor for MM ON
    11 - 12 MM03_XY_2 Pt4w temperature sensor for MM ON
    13 - 14 MM03_XY_3 Pt4w temperature sensor for MM ON
    15 - 16 MM03_XY_4 Pt4w temperature sensor for MM ON
    17 - 18 MM01_UV_1 Pt4w temperature sensor for MM ON
    19 - 20 MM01_UV_2 Pt4w temperature sensor for MM ON
    21 - 22 MM01_UV_3 Pt4w temperature sensor for MM ON
    23 - 24 MM01_UV_4 Pt4w temperature sensor for MM ON
    25 - 26 MM01_XY_1 Pt4w temperature sensor for MM OFF
    27 - 28 MM01_XY_2 Pt4w temperature sensor for MM OFF
    29 - 30 MM01_XY_3 Pt4w temperature sensor for MM OFF
    31 - 32 MM01_XY_4 Pt4w temperature sensor for MM ON
    33 - 34 MM02_XY_1 Pt4w temperature sensor for MM OFF
    35 - 36 MM02_XY_2 Pt4w temperature sensor for MM OFF
    37 - 38 MM02_UV_3 Pt4w temperature sensor for MM ON
    39 - 40 MM02_UV_4 Pt4w temperature sensor for MM ON
    41 - 42 MM02_XY_1 Pt4w temperature sensor for MM ON
    43 - 44 MM02_XY_2 Pt4w temperature sensor for MM ON
    45 - 46 MM02_XY_3 Pt4w temperature sensor for MM ON
    47 - 48 MM02_XY_4 Pt4w temperature sensor for MM ON
    49 DC01_BS_Y2 Pt2w temperature sensor for DC OFF
    50 DC01_TJ_V1 Pt2w temperature sensor for DC OFF
    51 DC01_BS_V2 Pt2w temperature sensor for DC OFF
    52 DC01_TJ_Y1 Pt2w temperature sensor for DC OFF
    59 Hum1_HALL Humidity sensor ON
    60 Patm_hall Atmospheric pressure sensor ON
    63 - 64 pt4w-elmb10-T64 Temperature sensor, point T2 ON

  • ELMB #11
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack
    Status: installed
    Comments: ELMB #11 and ELMB #12 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    1 mwpc_8X_6v_vmon Low voltage for MWPC station 8 ON
    2 mwpc_8X_6v_imon Low voltage for MWPC station 8 ON
    3 mwpc_8X_9v_vmon Low voltage for MWPC station 8 ON
    4 mwpc_8X_9v_imon Low voltage for MWPC station 8 ON
    5 mwpc_7X_6v_vmon Low voltage for MWPC station 7 ON
    6 mwpc_7X_6v_imon Low voltage for MWPC station 7 ON
    7 mwpc_7X_9v_vmon Low voltage for MWPC station 7 ON
    8 mwpc_7X_9v_imon Low voltage for MWPC station 7 ON
    9 mwpc_7V_6v_vmon Low voltage for MWPC station 7 ON
    10 mwpc_7V_6v_imon Low voltage for MWPC station 7 ON
    11 mwpc_7V_9v_vmon Low voltage for MWPC station 7 ON
    12 mwpc_7V_9v_imon Low voltage for MWPC station 7 ON
    13 mwpc_7U_6v_vmon Low voltage for MWPC station 7 ON
    14 mwpc_7U_6v_imon Low voltage for MWPC station 7 ON
    15 mwpc_7U_9v_vmon Low voltage for MWPC station 7 ON
    16 mwpc_7U_9v_imon Low voltage for MWPC station 7 ON
    17 mwpc_11U_6v_vmon Low voltage for MWPC station 11 ON
    18 mwpc_11U_6v_imon Low voltage for MWPC station 11 ON
    19 mwpc_11U_9v_vmon Low voltage for MWPC station 11 ON
    20 mwpc_11U_9v_imon Low voltage for MWPC station 11 ON
    21 mwpc_11V_6v_vmon Low voltage for MWPC station 11 ON
    22 mwpc_11V_6v_imon Low voltage for MWPC station 11 ON
    23 mwpc_11V_9v_vmon Low voltage for MWPC station 11 ON
    24 mwpc_11V_9v_imon Low voltage for MWPC station 11 ON
    25 mwpc_11X_6v_vmon Low voltage for MWPC station 11 ON
    26 mwpc_11X_6v_imon Low voltage for MWPC station 11 ON
    27 mwpc_11X_9v_vmon Low voltage for MWPC station 11 ON
    28 mwpc_11X_9v_imon Low voltage for MWPC station 11 ON

  • ELMB #12
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack
    Status: installed
    Comments: ELMB #11 and ELMB #12 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    1 mwpc_10V_6v_vmon Low voltage for MWPC station 10 ON
    2 mwpc_10V_6v_imon Low voltage for MWPC station 10 ON
    3 mwpc_10V_9v_vmon Low voltage for MWPC station 10 ON
    4 mwpc_10V_9v_imon Low voltage for MWPC station 10 ON
    5 mwpc_10U_6v_vmon Low voltage for MWPC station 10 ON
    6 mwpc_10U_6v_imon Low voltage for MWPC station 10 ON
    7 mwpc_10U_9v_vmon Low voltage for MWPC station 10 ON
    8 mwpc_10U_9v_imon Low voltage for MWPC station 10 ON
    9 mwpc_10X_6v_vmon Low voltage for MWPC station 10 ON
    10 mwpc_10X_6v_imon Low voltage for MWPC station 10 ON
    11 mwpc_10X_9v_vmon Low voltage for MWPC station 10 ON
    12 mwpc_10X_9v_imon Low voltage for MWPC station 10 ON
    13 mwpc_9X_6v_vmon Low voltage for MWPC station 9 ON
    14 mwpc_9X_6v_imon Low voltage for MWPC station 9 ON
    15 mwpc_9X_9v_vmon Low voltage for MWPC station 9 ON
    16 mwpc_9X_9v_imon Low voltage for MWPC station 9 ON
    17 mwpc_9V_6v_vmon Low voltage for MWPC station 9 ON
    18 mwpc_9V_6v_imon Low voltage for MWPC station 9 ON
    19 mwpc_9V_9v_vmon Low voltage for MWPC station 9 ON
    20 mwpc_9V_9v_imon Low voltage for MWPC station 9 ON
    21 mwpc_9U_6v_vmon Low voltage for MWPC station 9 ON
    22 mwpc_9U_6v_imon Low voltage for MWPC station 9 ON
    23 mwpc_9U_9v_vmon Low voltage for MWPC station 9 ON
    24 mwpc_9U_9v_imon Low voltage for MWPC station 9 ON
    25 mwpc_8V_6v_vmon Low voltage for MWPC station 8 ON
    26 mwpc_8V_6v_imon Low voltage for MWPC station 8 ON
    27 mwpc_8V_9v_vmon Low voltage for MWPC station 8 ON
    28 mwpc_8V_9v_imon Low voltage for MWPC station 8 ON
    29 mwpc_8U_6v_vmon Low voltage for MWPC station 8 ON
    30 mwpc_8U_6v_imon Low voltage for MWPC station 8 ON
    31 mwpc_8U_9v_vmon Low voltage for MWPC station 8 ON
    32 mwpc_8U_9v_imon Low voltage for MWPC station 8 ON
    63 - 64 pt4w_elmb12_T64 Temperature inside hall 888, T7 OFF

  • ELMB #13
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack
    Status: installed
    Comments: ELMB #13 and ELMB #14 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    1 mwpc_6X_6v_vmon Low voltage for MWPC station 6 ON
    2 mwpc_6X_6v_imon Low voltage for MWPC station 6 ON
    3 mwpc_6X_9v_vmon Low voltage for MWPC station 6 ON
    4 mwpc_6X_9v_imon Low voltage for MWPC station 6 ON
    5 mwpc_5V_6v_vmon Low voltage for MWPC station 5 ON
    6 mwpc_5V_6v_imon Low voltage for MWPC station 5 ON
    7 mwpc_5V_9v_vmon Low voltage for MWPC station 5 ON
    8 mwpc_5V_9v_imon Low voltage for MWPC station 5 ON
    9 mwpc_2U_6v_vmon Low voltage for MWPC station 2 ON
    10 mwpc_2U_6v_imon Low voltage for MWPC station 2 ON
    11 mwpc_2U_9v_vmon Low voltage for MWPC station 2 ON
    12 mwpc_2U_9v_imon Low voltage for MWPC station 2 ON
    13 mwpc_2V_6v_vmon Low voltage for MWPC station 2 ON
    14 mwpc_2V_6v_imon Low voltage for MWPC station 2 ON
    15 mwpc_2V_9v_vmon Low voltage for MWPC station 2 ON
    16 mwpc_2V_9v_imon Low voltage for MWPC station 2 ON
    17 mwpc_2X_6v_vmon Low voltage for MWPC station 2 ON
    18 mwpc_2X_6v_imon Low voltage for MWPC station 2 ON
    19 mwpc_2X_9v_vmon Low voltage for MWPC station 2 ON
    20 mwpc_2X_9v_imon Low voltage for MWPC station 2 ON
    21 mwpc_3X_6v_vmon Low voltage for MWPC station 3 ON
    22 mwpc_3X_6v_imon Low voltage for MWPC station 3 ON
    23 mwpc_3X_9v_vmon Low voltage for MWPC station 3 ON
    24 mwpc_3X_9v_imon Low voltage for MWPC station 3 ON
    25 mwpc_3U_6v_vmon Low voltage for MWPC station 3 ON
    26 mwpc_3U_6v_imon Low voltage for MWPC station 3 ON
    27 mwpc_3U_9v_vmon Low voltage for MWPC station 3 ON
    28 mwpc_3U_9v_imon Low voltage for MWPC station 3 ON
    29 mwpc_3V_6v_vmon Low voltage for MWPC station 3 ON
    30 mwpc_3V_6v_imon Low voltage for MWPC station 3 ON
    31 mwpc_3V_9v_vmon Low voltage for MWPC station 3 ON
    32 mwpc_3V_9v_imon Low voltage for MWPC station 3 ON
    63 - 64 pt4w_elmb13_T64 Pt4w temperature sensor OFF

  • ELMB #14
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, MWPC power supply rack
    Status: installed.
    Comments: ELMB #13 and ELMB #14 are mounted in one box and have common power supply and external wiring for all CANbus signals.
    ADC channels Dp name Comments Status
    1 mwpc_4U_6v_vmon Low voltage for MWPC station 4 ON
    2 mwpc_4U_6v_imon Low voltage for MWPC station 4 ON
    3 mwpc_4U_9v_vmon Low voltage for MWPC station 4 ON
    4 mwpc_4U_9v_imon Low voltage for MWPC station 4 ON
    5 mwpc_4V_6v_vmon Low voltage for MWPC station 4 ON
    6 mwpc_4V_6v_imon Low voltage for MWPC station 4 ON
    7 mwpc_4V_9v_vmon Low voltage for MWPC station 4 ON
    8 mwpc_4V_9v_imon Low voltage for MWPC station 4 ON
    9 mwpc_4X_6v_vmon Low voltage for MWPC station 4 ON
    10 mwpc_4X_6v_imon Low voltage for MWPC station 4 ON
    11 mwpc_4X_9v_vmon Low voltage for MWPC station 4 ON
    12 mwpc_4X_9v_imon Low voltage for MWPC station 4 ON
    13 mwpc_5X_6v_vmon Low voltage for MWPC station 5 ON
    14 mwpc_5X_6v_imon Low voltage for MWPC station 5 ON
    15 mwpc_5X_9v_vmon Low voltage for MWPC station 5 ON
    16 mwpc_5X_9v_imon Low voltage for MWPC station 5 ON
    17 mwpc_5U_6v_vmon Low voltage for MWPC station 5 ON
    18 mwpc_5U_6v_imon Low voltage for MWPC station 5 ON
    19 mwpc_5U_9v_vmon Low voltage for MWPC station 5 ON
    20 mwpc_5U_9v_imon Low voltage for MWPC station 5 ON
    25 mwpc_6V_6v_vmon Low voltage for MWPC station 6 ON
    26 mwpc_6V_6v_imon Low voltage for MWPC station 6 ON
    27 mwpc_6V_9v_vmon Low voltage for MWPC station 6 ON
    28 mwpc_6V_9v_imon Low voltage for MWPC station 6 ON
    29 mwpc_6U_6v_vmon Low voltage for MWPC station 6 ON
    30 mwpc_6U_6v_imon Low voltage for MWPC station 6 ON
    31 mwpc_6U_9v_vmon Low voltage for MWPC station 6 ON
    32 mwpc_6U_9v_imon Low voltage for MWPC station 6 ON
    63 - 64 pt4w_elmb14_T64 Pt4w temperature sensor inside hall 888, T8 ON

  • ELMB #15
    CANbus line #2
    ADC mode:unipolar; ADC range: 100 mV.
    Place: bld. 888, on gallery, Jura side
    Status: installed.
    ADC channels Dp name Comments Status
    1 mwpc_1X_6v_vmon Low voltage for MWPC station 1 ON
    2 mwpc_1X_6v_imon Low voltage for MWPC station 1 ON
    3 mwpc_1X_9v_vmon Low voltage for MWPC station 1 ON
    4 mwpc_1X_9v_imon Low voltage for MWPC station 1 ON
    5 mwpc_1Y_6v_vmon Low voltage for MWPC station 1 ON
    6 mwpc_1Y_6v_imon Low voltage for MWPC station 1 ON
    7 mwpc_1Y_9v_vmon Low voltage for MWPC station 1 ON
    8 mwpc_1Y_9v_imon Low voltage for MWPC station 1 ON
    9 mwpc_1V_6v_vmon Low voltage for MWPC station 1 ON
    10 mwpc_1V_6v_imon Low voltage for MWPC station 1 ON
    11 mwpc_1V_9v_vmon Low voltage for MWPC station 1 ON
    12 mwpc_1V_9v_imon Low voltage for MWPC station 1 ON
    13 mwpc_1U_6v_vmon Low voltage for MWPC station 1 ON
    14 mwpc_1U_6v_imon Low voltage for MWPC station 1 ON
    15 mwpc_1U_9v_vmon Low voltage for MWPC station 1 ON
    16 mwpc_1U_9v_imon Low voltage for MWPC station 1 ON
    63 - 64 pt4w-elmb15-T64 Pt4w temperature sensor inside hall 888, T10 ON

  • ELMB #16
    CANbus line #1
    ADC mode: bipolar; ADC range: 1 V.
    Place: Trigger room HNB422
    Status: installed.
    Comments: Automated system for Gas distribution in the area provides 3 switches. A small current is injected to give the signal (closed=on=alarm). Also PS for Veto Box gives current and voltage (scaling factors applied in PVSS according to the PS info -> 1V=0.4A and 1V=3.33 KV).
    ADC channels Dp name Comments Status
    1 - 2 Temp_NIM_1 Pt4w temperature sensor, inside ELMB box ON
    58 VBX_PS_V Voltage from Veto Box PS unit ON
    59 VBX_PS_I Current from Veto Box PS unit ON
    62 Gas_lv3_alarm Level 3 alarm from Gas gen. distrib. system ON
    63 Gas_gen_alarm General alarm from Gas gen. distrib. system ON
    64 Gas_lv2_alarm Level 2 alarm from Gas gen. distrib. system ON

  • ELMB #17
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, STRAW frame, close to ELMB #6 (?)
    Status: installed (?)

  • ELMB #18
    CANbus line #1
    ADC mode: bipolar; ADC range: 1 V.
    Place: Trigger room HNB429
    Status: installed, but NOT connected to sensors, NO Data Points in PVSS (?).

  • ELMB #19
    CANbus line #1
    ADC mode: unipolar; ADC range 100 mV.
    Place: bld. 888, beam area downstream, MW2 power supply rack.
    Status: installed.
    ADC channels Dp name Comments Status
    1 LAX1_N1 Amplifier for X1, mW2 low voltage PS ON
    2 LAX1_N2 Amplifier for X1, mW2 low voltage PS ON
    3 LAX1_P Amplifier for V1, mW2 low voltage PS ON
    4 LTX1_P Amplifier for V1, mW2 low voltage PS ON
    5 LAY1_N1 Amplifier for X2, mW2 low voltage PS ON
    6 LAY1_P Amplifier for X2, mW2 low voltage PS ON
    7 LTY1_P Amplifier for V2, mW2 low voltage PS ON
    8 LAU1_N1 Amplifier for V2, mW2 low voltage PS ON
    9 LAU1_N2 Not used OFF
    10 LAU1_P Amplifier for Y1, mW2 low voltage PS ON
    11 LTU1_P Not used OFF
    12 LAX2_N1 Amplifier for Y2, mW2 low voltage PS ON
    13 LAX2_N2 TDC for X,V, mW2 low voltage PS ON
    14 LAX2_P Thresholds Y1,Y2, mW2 low voltage PS ON
    15 LTX2_P TDC for Y, mW2 low voltage PS ON
    16 LAY2_N1 Not used OFF
    17 LAY2_P Thresholds X1,V1, mW2 low voltage PS ON
    18 LTY2_P Thresholds X2,V2, mW2 low voltage PS ON
    19 LAU2_N1 Not used OFF
    20 LAU2_N2 Not used OFF
    21 LAU2_P Not used OFF
    22 LTU2_P Not used OFF
    63 - 64 pt4w_elmb19_T64 Pt4w temperature sensor, T7 ON

  • ELMB #20
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, W45 power supply rack.
    Status: installed.
    ADC channels Dp name Comments Status
    1 W5_1_6V voltage, low voltage PS for W45 ON
    2 W5_1_6A current, low voltage PS for W45 ON
    3 W5_1_9V voltage, low voltage PS for W45 ON
    4 W5_1_9A current, low voltage PS for W45 ON
    5 W5_2_6V voltage, low voltage PS for W45 ON
    6 W5_2_6A current, low voltage PS for W45 ON
    7 W5_2_9V voltage, low voltage PS for W45 ON
    8 W5_2_9A current, low voltage PS for W45 ON
    9 W4_1_6V voltage, low voltage PS for W45 ON
    10 W4_1_6A current, low voltage PS for W45 ON
    11 W4_1_9V voltage, low voltage PS for W45 ON
    12 W4_1_9A current, low voltage PS for W45 ON
    13 W4_2_6V voltage, low voltage PS for W45 ON
    14 W4_2_6A current, low voltage PS for W45 ON
    15 W4_2_9V voltage, low voltage PS for W45 ON
    16 W4_2_9A current, low voltage PS for W45 ON
    17 W2_1_6V voltage, low voltage PS for W45 ON
    18 W2_1_6A current, low voltage PS for W45 ON
    19 W2_1_9V voltage, low voltage PS for W45 ON
    20 W2_1_9A current, low voltage PS for W45 ON
    21 W2_2_6V voltage, low voltage PS for W45 ON
    22 W2_2_6A current, low voltage PS for W45 ON
    23 W2_2_9V voltage, low voltage PS for W45 ON
    24 W2_2_9A current, low voltage PS for W45 ON
    25 W1_1_6V voltage, low voltage PS for W45 ON
    26 W1_1_6A current, low voltage PS for W45 ON
    27 W1_1_9V voltage, low voltage PS for W45 ON
    28 W1_1_9A current, low voltage PS for W45 ON
    29 W1_2_6V voltage, low voltage PS for W45 ON
    30 W1_2_6A current, low voltage PS for W45 ON
    31 W1_2_9V voltage, low voltage PS for W45 ON
    32 W1_2_9A current, low voltage PS for W45 ON
    33 - 34 DW05_jura Pt4w temperature sensor on W45 OFF
    35 - 36 DW05_bottom Pt4w temperature sensor on W45 OFF
    37 - 38 DW05_saleve Pt4w temperature sensor on W45 OFF
    39 - 40 DW05_electr Pt4w temperature sensor on W45 OFF
    41 - 42 DW06_jura Pt4w temperature sensor on W45 OFF
    43 - 44 DW06_bottom Pt4w temperature sensor on W45 OFF
    45 - 46 DW06_saleve Pt4w temperature sensor on W45 OFF
    47 - 48 DW06_electr Pt4w temperature sensor on W45 OFF

  • ELMB #21
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Straw station 5 frame.
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 ST05X1_TDS Pt4w temp sensor, Straw station 5 ON
    3 - 4 ST05X1_TDM Pt4w temp sensor, Straw station 5 ON
    5 - 6 ST05X1_TDJ Pt4w temp sensor, Straw station 5 ON
    7 - 8 ST05X1_TMS Pt4w temp sensor, Straw station 5 ON
    9 - 10 ST05X1_TMJ Pt4w temp sensor, Straw station 5 ON
    11 - 12 ST05X1_TUS Pt4w temp sensor, Straw station 5 ON
    13 - 14 ST05X1_TUM Pt4w temp sensor, Straw station 5 ON
    15 - 16 ST05X1_TUJ Pt4w temp sensor, Straw station 5 ON
    17 - 18 ST05Y1_TDS Pt4w temp sensor, Straw station 5 ON
    19 - 20 ST05Y1_TDM Pt4w temp sensor, Straw station 5 ON
    21 - 22 ST05Y1_TDJ Pt4w temp sensor, Straw station 5 ON
    23 - 24 ST05Y1_TMS Pt4w temp sensor, Straw station 5 ON
    25 - 26 ST05Y1_TMJ Pt4w temp sensor, Straw station 5 ON
    27 - 28 ST05Y1_TUS Pt4w temp sensor, Straw station 5 ON
    29 - 30 ST05Y1_TUM Pt4w temp sensor, Straw station 5 ON
    31 - 32 ST05Y1_TUJ Pt4w temp sensor, Straw station 5 ON
    33 - 34 ST05U1_TDS Pt4w temp sensor, Straw station 5 ON
    35 - 36 ST05U1_TDM Pt4w temp sensor, Straw station 5 ON
    37 - 38 ST05U1_TDJ Pt4w temp sensor, Straw station 5 ON
    39 - 40 ST05U1_TMS Pt4w temp sensor, Straw station 5 ON
    41 - 42 ST05U1_TMJ Pt4w temp sensor, Straw station 5 ON
    43 - 44 ST05U1_TUS Pt4w temp sensor, Straw station 5 ON
    45 - 46 ST05U1_TUM Pt4w temp sensor, Straw station 5 ON
    47 - 48 ST05U1_TUJ Pt4w temp sensor, Straw station 5 ON
    49 ST05X1_H Humidity sensor, Straw station 5 ON
    50 ST05Y1_H Humidity sensor, Straw station 5 ON
    51 ST05U1_H Humidity sensor, Straw station 5 ON

  • ELMB #22
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, Straw station 6 frame.
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 ST06V1_TDS Pt4w temp sensor, Straw station 6 ON
    3 - 4 ST06V1_TDM Pt4w temp sensor, Straw station 6 OFF
    5 - 6 ST06V1_TDJ Pt4w temp sensor, Straw station 6 ON
    7 - 8 ST06V1_TMS Pt4w temp sensor, Straw station 6 ON
    9 - 10 ST06V1_TMJ Pt4w temp sensor, Straw station 6 ON
    11 - 12 ST06V1_TUS Pt4w temp sensor, Straw station 6 ON
    13 - 14 ST06V1_TUM Pt4w temp sensor, Straw station 6 ON
    15 - 16 ST06V1_TUJ Pt4w temp sensor, Straw station 6 ON
    17 - 18 ST06Y1_TDS Pt4w temp sensor, Straw station 6 ON
    19 - 20 ST06Y1_TDM Pt4w temp sensor, Straw station 6 ON
    21 - 22 ST06Y1_TDJ Pt4w temp sensor, Straw station 6 ON
    23 - 24 ST06Y1_TMS Pt4w temp sensor, Straw station 6 ON
    25 - 26 ST06Y1_TMJ Pt4w temp sensor, Straw station 6 ON
    27 - 28 ST06Y1_TUS Pt4w temp sensor, Straw station 6 ON
    29 - 30 ST06Y1_TUM Pt4w temp sensor, Straw station 6 ON
    31 - 32 ST06Y1_TUJ Pt4w temp sensor, Straw station 6 ON
    33 - 34 ST06X1_TDS Pt4w temp sensor, Straw station 6 ON
    35 - 36 ST06X1_TDM Pt4w temp sensor, Straw station 6 ON
    37 - 38 ST06X1_TDJ Pt4w temp sensor, Straw station 6 ON
    39 - 40 ST06X1_TMS Pt4w temp sensor, Straw station 6 ON
    41 - 42 ST06X1_TMJ Pt4w temp sensor, Straw station 6 ON
    43 - 44 ST06X1_TUS Pt4w temp sensor, Straw station 6 ON
    45 - 46 ST06X1_TUM Pt4w temp sensor, Straw station 6 ON
    47 - 48 ST06X1_TUJ Pt4w temp sensor, Straw station 6 ON
    49 ST06V1_H Humidity sensor, Straw station 6 ON
    50 ST06Y1_H Humidity sensor, Straw station 6 ON
    51 ST06X1_H Humidity sensor, Straw station 6 OFF

  • ELMB #23
    CANbus line #1
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, (?).
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 DW01_UP Pt4w temperature sensor OFF
    3 - 4 DW01_DOWN Pt4w temperature sensor ON
    5 - 6 DW01_RIGHT Pt4w temperature sensor ON
    7 - 8 DW01_LEFT Pt4w temperature sensor ON
    9 - 10 DW02_UP Pt4w temperature sensor ON
    11 - 12 DW02_DOWN Pt4w temperature sensor ON
    13 - 14 DW02_LEFT Pt4w temperature sensor ON
    15 - 16 DW02_RIGHT Pt4w temperature sensor ON
    17 - 18 DW03_UP Pt4w temperature sensor ON
    19 - 20 DW03_DOWN Pt4w temperature sensor ON
    21 - 22 DW03_LEFT Pt4w temperature sensor ON
    23 - 24 DW03_RIGHT Pt4w temperature sensor ON
    25 - 26 DW04_UP Pt4w temperature sensor ON
    27 - 28 DW04_DOWN Pt4w temperature sensor ON
    29 - 30 DW04_LEFT Pt4w temperature sensor ON
    31 - 32 DW04_RIGHT Pt4w temperature sensor OFF
    33 - 34 DW05_UP Pt4w temperature sensor OFF
    35 - 36 DW05_DOWN Pt4w temperature sensor ON
    37 - 38 DW05_LEFT Pt4w temperature sensor ON
    39 - 40 DW05_RIGHT Pt4w temperature sensor ON
    41 - 42 DW06_UP Pt4w temperature sensor ON
    43 - 44 DW06_DOWN Pt4w temperature sensor ON
    45 - 46 DW06_LEFT Pt4w temperature sensor ON
    47 - 48 DW06_RIGHT Pt4w temperature sensor ON

  • ELMB #24
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, (?).
    Status: installed.
    ADC channels Dp name Comments Status
    3 - 4 DC02_TS_U3 Pt4w temperature sensor ON
    5 - 6 DC02_2 Pt4w temperature sensor OFF
    7 - 8 DC02_BS_X1 Pt4w temperature sensor ON
    9 - 10 DC02_4 Pt4w temperature sensor OFF
    17 DC03_2 Pt2w temperature sensor OFF
    18 DC03_1 Pt2w temperature sensor OFF
    19 DC03_3 Pt2w temperature sensor OFF

  • ELMB #25
    CANbus line #2
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, (?).
    Status: installed.
    ADC channels Dp name Comments Status
    1 - 2 pt4w_RICH_32 Pt4w temperature sensor OFF
    3 - 4 pt4w_RICH_33 Pt4w temperature sensor OFF
    5 - 6 pt4w_RICH_34 Pt4w temperature sensor OFF
    7 - 8 pt4w_RICH_35 Pt4w temperature sensor OFF
    9 - 10 pt4w-RICH-36 Pt4w temperature sensor OFF
    11 - 12 pt4w-RICH-37 Pt4w temperature sensor OFF
    13 - 14 pt4w-RICH-38 Pt4w temperature sensor OFF
    15 - 16 pt4w-RICH-39 Pt4w temperature sensor OFF
    17 - 18 pt4w-RICH-40 Pt4w temperature sensor OFF
    19 - 20 pt4w-RICH-41 Pt4w temperature sensor OFF
    21 - 22 pt4w-RICH-42 Pt4w temperature sensor OFF
    23 - 24 pt4w-RICH-43 Pt4w temperature sensor OFF
    25 - 26 pt4w-RICH-44 Pt4w temperature sensor OFF
    27 - 28 pt4w-RICH-45 Pt4w temperature sensor OFF
    29 - 30 pt4w-RICH-46 Pt4w temperature sensor OFF
    31 - 32 pt4w-RICH-47 Pt4w temperature sensor OFF
    33- 34 pt4w-RICH-48 Pt4w temperature sensor OFF
    35- 36 pt4w-RICH-49 Pt4w temperature sensor OFF
    37- 38 pt4w-RICH-50 Pt4w temperature sensor OFF
    39 - 40 pt4w-RICH-51 Pt4w temperature sensor OFF
    41 - 42 pt4w-RICH-52 Pt4w temperature sensor OFF

  • ELMB #26
    CANbus line #3
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, beam area, small silicon rack under target platform.
    Comments: ELMB installed inside ELMB box belonging to Silicon group.
    Status: installed.
    ADC channels Dp name Comments Status
    1 SI03_T_u1 Pt4w temperature sensor ON
    2 SI03_T_v1 Pt4w temperature sensor ON
    3 SI03_T_v2 Pt4w temperature sensor ON
    4 SI03_T_x1 Pt4w temperature sensor ON
    5 SI03_T_y1 Pt4w temperature sensor ON
    6 SI03_T_y2 Pt4w temperature sensor ON

  • ELMB #27
    CANbus line #3
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, beam area, small silicon rack under target platform.
    Comments: ELMB installed inside ELMB box belonging to Silicon group.
    Status: installed.
    ADC channels Dp name Comments Status
    1 SI04_T_u1 Pt4w temperature sensor ON
    2 SI04_T_v1 Pt4w temperature sensor ON
    3 SI04_T_v2 Pt4w temperature sensor ON
    4 SI04_T_x1 Pt4w temperature sensor ON
    5 SI04_T_y1 Pt4w temperature sensor ON
    6 SI04_T_y2 Pt4w temperature sensor ON

  • ELMB #28
    CANbus line #3
    ADC mode: unipolar; ADC range: 100 mV.
    Place: bld. 888, beam area, small silicon rack under target platform.
    Comments: ELMB installed inside ELMB box belonging to Silicon group.
    Status: installed.
    ADC channels Dp name Comments Status
    1 SI05_T_u1 Pt4w temperature sensor ON
    2 SI05_T_v1 Pt4w temperature sensor ON
    3 SI05_T_v2 Pt4w temperature sensor ON
    4 SI05_T_x1 Pt4w temperature sensor ON
    5 SI05_T_y1 Pt4w temperature sensor ON
    6 SI05_T_y2 Pt4w temperature sensor ON

Last update: 13 October 2004